A - Upstream pressure point
B - Downstream pressure point
R
I - Gas valve electrical connection
R - Gas outlet
S - Gas inlet
B
I
A
TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A
S
fig. 18 - Gas valve
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 9.1). Press the
heating buttons detail 3 - fig. 25 to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 9.1).
Configuration Menu
Press the DHW buttons together for 10 seconds to access the configuration Menu. 7 pa-
rameters are available, indicated by the letter "b", which are not modifiable from Remote
Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.
Contents
Description
Range
0=Natural Gas
b01
Gas type selection
1=LPG
1=Bithermal instanta-
neous
2=Monothermal
instantaneous
b02
Boiler type selection
3=Heating only (3-
way valve)
4=Heating only (cir-
culating pump)
0=Sealed Chamber
combustion control
(without fume pres-
sure switch)
1=Open Chamber
(with fume thermo-
stat)
2=Sealed Chamber
(with fume pressure
switch)
3=Sealed Chamber
Combustion cham-
b03
combustion control
ber type selection
(with fume thermostat
on recuperator)
4=LOW NOx Sealed
Chamber combus-
tion control
(without fume pres-
sure switch)
5=LOW NOx Open
Chamber
(with fume thermo-
stat)
18
EN
~ 24Ω
fig. 19 - Gas valve connection
Default
CLIZIA D 32 AS
0=Natural Gas
0=Natural Gas
1=Bithermal instanta-
2=Monothermal
neous
instantaneous
0=Sealed Chamber
0=Sealed Chamber
with
with
combustion control
combustion control
(without fume pres-
sure switch)
cod. 3541C820 - Rev. 00 - 09/2012
Contents
Description
Primary Exchanger
type selection
(b03=0)
No effect on adjust-
ment (b03=1)
No effect on adjust-
ment (b03=2)
b04
Primary Exchanger
type selection
~ 65Ω
(b03=3)
No effect on adjust-
ment (b03=4)
No effect on adjust-
ment (b03=5)
Relay card LC32
operation selection
(b02=1)
No effect on adjust-
b05
ment (b02=2)
No effect on adjust-
ment (b02=3)
No effect on adjust-
ment (b02=4)
Mains Voltage Fre-
b06
quency
Comfort burner on
time
(b02=1)
No effect on adjust-
ment (b02=2)
b07
No effect on adjust-
ment (b02=3)
No effect on adjust-
ment (b02=4)
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.
Service menu
The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu, "Hi" means History Menu: after selecting the submenu, press the Re-
set button again to access it; "rE" means History Menu Reset: see description.
"tS" - Transparent Parameters Menu
16 parameters indicated by the letter "P" are available: which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.
Contents
Description
P01
Ignition ramp Offset
P02
Heating ramp
P03
Heating standby time 0-10 minutes
Heating Post-Circula-
P04
tion
Heating user max.
P05
setpoint
Max. power in heat-
P06
ing
CLIZIA D 32 AS
Range
Default
0=Flat
1=Omega
0=Flat
0=Flat
2=--
--
0
--
0
0=Flat
1=Omega
0=Flat
2=--
--
0
--
0
0=External gas valve
1=System filling sole-
0=External gas valve 0=External gas valve
noid valve
2=Solar 3-way
--
0
--
0
--
0
0=50Hz
0=50Hz
0=50Hz
1=60Hz
0-20 seconds
5 seconds
5 seconds
--
5
--
5
--
5
Range
Default
0-40
10
10
1-20°C/minute
5°C/minute
5°C/minute
2 minutes
2 minutes
0-20 minutes
6 minutes
6 minutes
31-85°C
80°C
80°C
0-100%
100%
100%
CLIZIA D 32 AS
CLIZIA D 32 AS