SN2005/IR
Rough-In Dimensions for Supplies and Drain
Notes
Maximum flow rate required to washfountain is 1.5 GPM (5.7 LPM). Size supply lines
accordingly.
Supplies from Below: Stub up 2-1/2" (64).
Supplies from Above: Supplies must be located on centers of dimensions shown to pass
through washfountain shroud and sprayhead.
Drain through floor: Stub up 3" (76).
Supplies from Below or Through Wall
Top View
3-1/4" (83)
Remote mounting of transformers with 24VAC electrical
supply to washfountain is recommended.
UPC and IPC restrict the vertical distance from the
fixture outlet to the trap weir to not more than 24" (610).
Check state and local codes for variances.
Standard height floor-mounted models
with Infrared or hand control are ADA
compliant.
4
Type A
Off-line vent (P-Trap
supplied by Installer.)
Type H
Centrally rising vent (P-Trap furnished
with unit.) Use for units with paper towel
Dispensers and/or shrouds.
4-1/2"
4-1/2"
(114)
(114)
H
C
Type H
5"
4"
(127)
(102)
Type A
6/29/12
Key
1/2" Supply: Nominal Copper Tube
1/2" Supply: Nominal Copper Tube
1-1/2" NPT Drain Stub up 3" (76) from Floor
1-1/2" NPT Drain Stub up 3" (76) from Floor
Conduit Location (Recommended)
Conduit Location (Recommended
Supplies from Above
Type B
Centrally rising vent (P-Trap furnished
with unit.) Use for units with paper towel
Dispensers and/or shrouds.
Type O
Off-line vent (P-Trap
supplied by Installer.)
Top View
4" (102)
27/32" (21)
H
27/32" (21)
5"
(127)
C
1-3/16"
(30)
Bradley • 215-1067 Rev. H; ECN 12-00-011
Installation
(mm)
)
Type B
Type O