Faults; Dismounting, Return And Disposal - WIKA XTRACTO-PAD TC59-X Manual De Instrucciones

Ocultar thumbs Ver también para XTRACTO-PAD TC59-X:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8. Faults / 9. Dismounting, return and disposal

8. Faults

Faults
No signal/line breakage
Erroneous
measured values (of
thermocouples)
Signal interference
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the
instrument immediately, and ensure that pressure and/or signal are no longer present,
and secure the instrument from being put back into operation inadvertently.
In this case, contact the manufacturer.
If a return is needed, please follow the instructions see chapter 9.2 "Return".

9. Dismounting, return and disposal

WARNING!
Residual media in the dismounted instrument can result in a risk to persons, the
environment and equipment. Take sufficient precautionary measures.
9.1 Dismounting
WARNING!
Risk of burns!
Let the instrument cool down sufficiently before dismounting it!
During dismounting there is a risk of dangerously hot pressure media escaping.
Only disconnect the instrument once the system has been depressurised!
WIKA operating instructions model TC59-X (XTRACTO-PAD
Causes
Mechanical load too high or
overtemperature
Parasitic voltages (thermal
voltages, galvanic voltage) or
incorrect thermocouple cable type
Stray currents caused by electric
fields or earth loops
Earth circuits
Measures
Replace probe or measuring insert
with a suitable design
Use the correct thermocouple
cable type
Use of shielded connecting cables,
increase in the distance to motors
and power lines
Elimination of potentials, use of
galvanically isolated transmitter
supply isolators or transmitters
)
EN
19

Publicidad

Tabla de contenido
loading

Tabla de contenido