Zone Setup
Assign Load Type
1. Enter programming mode (see page 12).
Main menu
2. Use the master buttons to highlight "Zone
setup" and press the OK button to
Occ sensor
accept.
Zone setup
3. Use the master buttons to highlight "Load
type". Press the OK button to accept.
Zone setup
4. Use the zone raise/lower buttons to
choose the load type for that zone. See
Load type
the list below for supported load types.
High end
Press the OK button to accept.
5. The info screen will display a
confirmation screen that your load type
Load type
has been saved.
6. Exit programming mode (see page 12).
Set type using
zone controls
Saved
Saved
Setting Load Types
Fixture load type
Incandescent
MLV (magnetic low-voltage)
ELV (electronic low-voltage)
Hi-Lume / Eco-10
Non-dim
Neon/Cold cathode
Tu-Wire
R
Choose this load type from the menu
on the GRAFIK Eye
LUTRON
Direct control via
GRAFIK Eye QS
Incandescent
MLV
--
--
Non-dim LOFO or Non-dim FOFO
Neon, CC
Tu-Wire
QS:
®
LUTRON
Control via
power module
Power module
Power module
Power module
Fluorescent module
Non-dim LOFO or Non-dim FOFO
Neon, CC
Tu-Wire
GRAFIK Eye
®
OK
1
2
3
4
Load Type Notes
• All electronic low-voltage (ELV) lighting
used with an interface must be rated for
reverse phase control dimming. Before
installing an ELV light source, verify with
the manufacturer that their transformer
can be dimmed. When dimming, an ELV
interface must be used with the control
unit.
• Not all zones must be connected;
however, connected zones must have a
minimum load of 25 W.
• No zone may be loaded with more than
800 W.
• Maximum total lighting load per unit is
16 A.
• Maximum total lighting load for a
magnetic low-voltage (MLV) load is
2000 VA or 1600 W after transformer.
Maximum load per MLV zone is 800 VA
or 600 W.
QS System Installation and Operation Guide 8
Master
buttons
OK
button
5
6
Use the
zone
raise/lower
buttons to
choose the
load type for
that zone.