6. Trouble Shooting
Use the table below to solve minor problems.
Problem
Possible Cause
LED display on the front
Low battery
panel does not work.
Battery fault
The UPS is not turned on.
Alarm continuously
The UPS is overload.
sounds when the
mains is normal.
When power fails,
The UPS is overload.
back-up time is shorten.
Battery voltage is too low.
Battery defect. It might be due to
high temperature operation
environment, or improper
operation to battery.
The mains is normal
Power cord is loose.
Bu the unit is on
battery mode.
7 Specifications
Model
CAPACITY
INPUT
Voltage
Voltage Range
OUTPUT
Voltage Regulation
Transfer Time
Waveform
BATTERY
Type & Number
Charging Time
PHYSICAL
Dimension (DxWxH)
Net Weight (kgs)
Environment
0-90 % RH @ 0-40° C (non-condensing)
Humidity
Noise Level
MANAGEMENT
USB/RS-232 (Option)
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux,
Solutions
Charge the UPS at least 6 hours.
Replace the battery with the same type of
battery.
Press the power switch again to turn on
the UPS.
Remove some loads first. Before
reconnecting equipment, please verify
that the load matches the UPS capability
specified in the specs.
Remove some critical load. Entfernen Sie
nicht notwendige Spannungsgeräte.
Charge the UPS at least 6 hours.
Replace the battery with the same type of
battery.
Reconnect the power cord properly.
EP 1000
1000 VA / 600 W
110/120 VAC or 220/230/240 VAC
81-145 VAC / 162-290 VAC
+/-10%
Typical 2-6 ms, 10 ms max.
Simulated Sine Wave
12 V/7 AH x 2
4-6 hours recover to 90% capacity
350 x 146 x 160 mm
8.0
Less than 40 dB
Unix, and MAC
4
Line Interactive UPS
1. Lieferumfang
Im Lieferumfang sollten Sie folgendes finden:
- USV Einheit
- Kurzanleitung
- Kommunikationskabel (nur für Modelle mit USB/RS-232 Schnittstelle)
- Netzkabel (nur für Modelle mit IEC-Eingang)
2. Produktü bersicht
Vorderansicht:
Rü ckansicht:
Quick Guide V.2.0
Ein/Aus Schalter
Betriebsanzeige: grün
Batteriemodus: gelb blinkend
Fehlermeldung: rot
Ausgänge
AC Eingang
Schutzschalter
Modem / Telefon /
Netzwerk Ü berspannungsschutz
RS-232 com. Schnittstelle
USB com. Schnittstelle
5
DE

Publicidad

Tabla de contenido
loading

Tabla de contenido