Plumb Dot Accuracy
GB
Checking the plumb calibration of the laser can be most
accurately done when there is a substantial amount of vertical
height available, ideally 25' (7.5 m), with one person on the floor
positioning the laser and another person near a ceiling to mark
the dot created by the beam on the ceiling.
1.
Mark point P1 on the floor (Figure
2.
Turn the laser ON and press
and below the laser.
3.
Place the laser so that the down dot is centered over point
P1 and mark the center of the up dot on the ceiling as point
P2 (Figure
#1).
H
4.
Turn the laser 180°, making sure that the down dot is still
centered on point P1 on the floor (Figure
5.
Mark the center of the up dot on the ceiling as point P3
(Figure
#2).
H
6.
Measure the distance between points P2 and P3.
7.
If your measurement is greater than the Allowable
Distance Between P2 & P3 for the corresponding
Distance Between Ceiling & Floor in the following table,
the laser must be serviced at an authorized service center.
Distance Between
Ceiling & Floor
4.5m (15')
6m (20')
9m (30')
12m (40')
10
Using the Laser
Operating Tips
• Always mark the center of the beam created by the laser.
• Extreme temperature changes may cause movement of
#1).
H
once to display dots above
• If the laser is ever dropped, check to make sure it is still
• As long as the laser is properly calibrated, the laser is self-
#2).
H
• Use the laser on a smooth, flat, level, surface.
Turning the Laser Off
Slide the Power/Transport Lock switch to the OFF/Locked
position (Figure
switch is not placed in the Locked position, the laser will not
turn off.
Using the Laser with Accessories
Allowable Distance
Between P2 & P3
3mm (1/8")
4.2mm (5/32")
6mm (1/4")
Only use Stanley accessories that are recommended for use
8.4mm (5/16")
with this model. Accessories that may be suitable for one laser
may create a risk of injury when used with another laser.
The bottom of the laser is equipped with 1/4-20 and 5/8-11
female threads (Figure
Stanley accessories. Only use Stanley accessories specified
for use with this laser. Follow the directions included with the
accessory.
Recommended accessories for use with this laser are available
at extra cost from your local dealer or authorized service center.
If you need assistance locating any accessory, please contact
your nearest Stanley service center or visit our website:
http://www.2helpU.com.
internal parts that can affect accuracy. Check your accuracy
often while working.
calibrated.
leveling. Each laser is calibrated at the factory to find level as
long as it is positioned on a flat surface within average ± 4°
of level. No manual adjustments are required.
#1a) when the laser is not in use. If the
A
WARNING:
Since accessories other than those offered by
Stanley have not been tested with this laser, use of
such accessories with this laser could be hazardous.
) to accommodate current or future
B