10.6
Requirement for supply lines and fuse
Ei'hil!l,i
DC-side
Max. conductor cross- 95 mm' (max. 120
section
mm')
Min. cable cross-sec- in accordance with local installation standards
tion
Length of insulation
Depending on the cable lug
to be stripped off
Tightening torque
15 -22 Nm
Recommended cable Solar cable
type
Fuse size (electrical
data)
Fuse size (mechanical mm
data)
Combiner box
External with DC isolator switch preferable
Cable diameter for
15 - 21 (M32) mm
cable fitting
Fitting for DC connec- M32
tion
Torque for cable fit-
4 Nm
ting
AC-side
Max. conductor cross-section
Max. cable cross-section (without wire sleeves)
Min. cable cross-section
Length of insulation to be stripped off
Tightening torque
Connection type
Ground conductor connection
Fuse protection for installation provided by customer
Fitting for AC connection
Cable diameter for cable fitting
Torque for cable fitting
Interfaces
Cable diameter for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Ethernet connection type
Torque for cable fitting
Kaco blueplanet 50.0TL3
Kaco blueplanet 60.0TL3
95 mm' (max. 120 95 mm' (max. 120
mm')
mm')
95mm'
95 mm' (AL or CU)
in accordance with local installation standards
25mm
lONm
Screw terminal
M8
min. 100 A / max.125 A
M63
32 - 42 mm
20Nm
11 - 17 (M25 ) 5 - 9.5 (M16) mm
Connector
0.25 - 1.5 mm'
RJ45
4 (M25 ) 1.5 (M16) Nm
K AC O
bl'hhh,i
15mm
-Nm
-Nm
1100V gPV max. 20A
14 x 5 1 mm
lntegrated DC isolator switch
1.8 - 2.75 (2mm' - 6mm') mm
SW15
1.8 Nm
0
newenergy.