GENERATOR USE
LD1H type
Receptacle No.4 and No.5 comprise
one 240V receptacle with two
powered terminals.
This generator is equipped with two
power generating circuits. When the
voltage selector switch is in the 120V/
240V position, each of the two power
producing circuits supplies power to
specific receptacles.
When the voltage selector switch is in
the 120V only position, you do not
need to spread the load over the
receptacles. Make sure the load on
any receptacle does not exceed its
available power shown below and the
total load does not exceed the total
current available.
Total Current Available:
30.0 A (EG4000CX)
37.5 A (EG5000CX)
45.8 A (EG6500CX∙EG6500CXS)
Receptacles
1
2
3
4
5
When the voltage selector switch is in the 120V/240V position, you
must balance the load. Divide the load between the two sets of
receptacles.
Set of Receptacles
1+3+5
2+4
24
EG4000CX
30 A
20 A
20 A
20 A
None
Total Current Available
15.0 A (EG4000CX)
18.8 A (EG5000CX)
22.9 A (EG6500CX∙
RECEPTACLE No.1
RECEPTACLE No.3
Available power
EG5000CX
EG6500CX∙EG6500CXS
30 A
20 A
20 A
30 A
None
EG6500CXS)
RECEPTACLE No.4
RECEPTACLE No.2
RECEPTACLE No.5
30 A
20 A
20 A
30 A
None