Par.
Description
5.01
LANGUAGE
5.02
UNITS OF PRESSURE
TRANSDUCER PRESSURE
5.04
MIN VALUE (4 mA)
TRANSDUCER PRESSURE
5.05
MAX VALUE (20 mA)
MINIMUM WORKING
5.08
FREQUENCY
MAXIMUM WORKING
5.09
FREQUENCY
5.10
PROPORTIONAL BOOST
MAXIMUM NUMBER OF
5.11
PUMPS ON
MAIN PUMP STOP DELAY
5.12
AUXILIARY START
5.13
FREQUENCY
5.14
AUXILIARY START DELAY
5.15
AUXILIARY STOP DELAY
5.16
CHANGEOVER TIME
Hours
5.17
PUMP KICK INTERVAL
Hours
5.18
DIGITAL INPUT 1
Programming
Units
Default
Min.
Spanish
English
French
Spanish
Italian
Portuguese
German
Bar
Bar
Bar - PSI - mwc
Bar
Wizard
-1
Bar
Wizard
5
Hz
25
10
Hz
50
25
Bar
0
0
8
1
Sec
10
10
Hz
49,5
25
Sec
2
1
Sec
2
1
24
OFF
24
OFF
Not used
Total Stop
Total Stop INV
Local Stop
Local Stop INV
Not used
IN Setpoint
IN Setpoint INV
Flow Sensor
Flow Sensor INV
Slave 0-10V
5. ADVANCED PARAMETERS
Max.
Dutch
Polish
You can select between different languages for the menu and the warnings.
Russian
Swedish
Units of working pressure on display.
10
Value of pressure transducer at 4mA
40
Value of pressure transducer at 20mA
50
Minimum frequency at which you allow the pump to work
65
Maximum frequency at which you allow the pump to work
MAX PUMP
Pressure boost at the maximum frequency of pump
PRESSURE
8
Maximum number of pumps that can function in the system simultaneously
Time from the moment the main pump is working at a speed below the stop
100
frequency (parameter 1.6) until it stops fully.
When the pump in operation reaches this frequency it sends a command to the
50
auxiliary to start up.
Time from the moment the condition of parameter 5.09 occurs until the auxiliary
200
pump starts.
Time from when a system of two or more pumps is working below parameter 1.6
10
until the auxiliary pumps stop.
72
Parameter to set time period for changeover between pumps.
Parameter to set time period for periodic start-up of pump.
72
If the pump is inactive for this set time period it will rotate at minimum frequency
for 2 or 3 times.
Selecting "Not used" will not affect the system.
We can use the digital input as a system start-stop or only one pump start-stop
choosing the Total Stop or Local Stop options.
It can also be used as a different default set pressure in the same way. Choosing IN
Setpoint you can be select another different set pressure on parameter 5.19.
Flow Sensor option is used when a flow sensor is available, which will stop the pump.
Slave 0-10V option is used if a 0-10V active device or a potentiometer (passive
device) is connected to the 0-10V input.
Note: INV options are used for NC inputs.
44