Saci pumps [e]motion Serie Manual De Instalación Y Mantenimiento página 45

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 1
Par.
Description
Units
5.19
PRESSURE IN 1
Bar
5.22
DIGITAL INPUT 2
5.23
PRESSURE IN 2
Bar
5.26
DIGITAL INPUT 3
5.27
PRESSURE IN 3
Bar
5.30
DIGITAL INPUT 4
5.31
PRESSURE IN 4
Bar
SLAVE 1V
5.35
Bar
PRESSURE SETPOINT
SLAVE 9V
5.36
Bar
PRESSURE SETPOINT
5.41
RELAY OUTPUT 1
5.42
RELAY OUTPUT 2
5.43
SCHEDULE OPERATION 1
5.44
PROGRAM START TIME 1
5.45
PROGRAM STOP TIME 1
5.46
SCHEDULE OPERATION 2
5.47
PROGRAM START TIME 2
5.48
PROGRAM STOP TIME 2
OVERPRESSURE ALERT
5.49
LEVEL
DRY RUNNING ALARM
5.54
ACTIVE
Programming
Default
Min.
Max.
4
0,5
FS
Not used
See parameter 5.18
4
0,5
FS
Not used
See parameter 5.18
4
0,5
FS
Not used
See parameter 5.18
4
0,5
FS
Par 1,1
0,5
Par. 5.05
Par 1,1
0,5
Par. 5.05
OFF
Alarm (NO)
Alarm (NC)
Start
Clock (NO)
OFF
Clock (NC)
Dry running
External stop
Overpressure (NO)
Overpressure (NC)
OFF
See parameter 5.41
OFF
M-Su
OFF
M-F
Sa-Su
M ..... Su
00:00
00:00
23:59
00:00
00:00
23:59
OFF
See parameter 5.43
00:00
00:00
23:59
00:00
00:00
23:59
FS
Par 1,1
FS
YES
YES
NO
45
A different setpoint can be set if the input is active.
See parameter 5.18
A different setpoint can be set if the input is active.
See parameter 5.18
A different setpoint can be set if the input is active.
See parameter 5.18
A different setpoint can be set if the input is active.
If a 0-10V device is installed, here you can set the pressure value for the 1 volt
signal.
*This parameter is available when any of the digital input is set to Slave 0-10V.
If a 0-10V device is installed, here you can set the pressure value for the 9 volt
signal.
*This parameter is available when any of the digital input is set to Slave 0-10V.
The aim of this parameter is to enable signals remotely.
OFF: The relay is never activated.
Alarm (NO): The relay closes before an alarm.
Alarm (NC): The relay opens before an alarm.
Start: The relay is energised when the unit is running.
Clock (NO): The relay closes depending on the time data programmed in
parameters 5.44 to 5.48.
Clock (NC): The relay opens depending on the time data programmed in
parameters 5.44 to 5.48.
Dry running: The relay is energised if the inverter detects dry running.
External stop: The relay is energised when there is an external stop. (For this
condition we must have programmed a digital input as "Local Stop").
Overpressure (NO): The relay closes if there is overpressure alert (par. 5.49).
Overpressure (NC): The relay opens if there is overpressure alert (par. 5.49).
See parameter 5.41
In this parameter you can choose not to have a schedule program (OFF) or the days
of the week that you want this program to run. You can choose between whole weeks
(M-Su), weekdays (M-F), weekends (Sa- Su) or individual days.
The schedule program will act on the output relay programmed for this purpose.
Start time of schedule program 1.
Stop time of schedule program 1.
Same as parameter 5.43 but for a second schedule program.
Start time of schedule program 2.
Stop time of schedule program 2.
Parameter to set the maximum pressure value of the Hydraulic system.
Parameter for enabling or disabling the low water level alarm.
In the case of being active and cause notice, the drive will start attempts by the
following sequence:
5 minutes, 15 minutes, 1 hour, 6 hours or 24 hours. The display shows the remaining
time start attempt. Pressing F2 we force the reset of the notice, still unfinished
countdown.
If after the 24-hour notice is detected again dry running, the drive will lock
indefinitely until you press F2.
EN
Notes

Publicidad

Tabla de contenido
loading

Productos relacionados para Saci pumps [e]motion Serie

Este manual también es adecuado para:

[e]motion mt2-11aE]motion tt3-11a[e]motion tt3-30a

Tabla de contenido