Register 51: State of output regulation CO2 On/off (state of alarm) [only read].
- 0: Output dissabled (relay contact open). No alarma.
- 1: Output activada (relay contact closed). Alarm.
Output On/off by potential-free relay contact. Output "Regulation CO2" On/off.
All / nothing output
Register 51
Register 52: State of output regulation CO2 proportional [only read].
The value that is sent is the value of the output percentage (0% to 100%) In binary 16 bits.
Analogic proportional Output 0...10V: Output "Regulation CO2" proportional.
Register 53: Remote stop [only read].
- 0: Remote stop disabled (open digital input).
- 1: Remote stop activated (digital input closed).
Register 54: Temperature [only read].
The value that is sent is the temperature value (0.0ºC to 50.0ºC) multiplied by 10 In binary 16 bits.
0,0ºC 0x0000
50,0ºC 0x01F4
Temperature sensor integrated in the regulator.
Proportional output [%]
Register 52
Maximum output [%]
Register 10
Minimum output [%]
Register 9
Hysteresis [ppm]
Register 6
Setpoint CO2 [ppm]
Register 3
Proportional band[%]
Register 7
Integration time [s]
Setpoint CO2 [ppm]
Registro 3
CO2 [ppm]
Register 30
Register 8
CO2 [ppm]
Registro 50