Correlation Between Gas Pressure And Burner Output; Gas Feeding Line - Riello 40 FS8 Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT

To obtain the maximum output, it is necessary to have 4.6 mbar measured on the pipe coupling,
with the combustion chamber at 0 mbar and gas G20 - Pci = 10 kWh/Nm
6
5
4
3
2
1
45
40.000

GAS FEEDING LINE

1
– Gas arrival pipe
1
(supplied by the installer)
– Manual gate
2
– Gas pressure gauge
3
– Filter
4
– Gas pressure switch
5
– Safety valve
6
– Pressure adjuster
7
GAS TRAIN ACCORDING TO EN 676
MULTIBLOC
MBDLE 405 B01
MBDLE 407 B01
The gas train is supplied separately, for its adjustment see the enclosed instructions.
3389
55
65
50.000
60.000
2
3
M1
(supplied by the installer)
CONNECTIONS
TRAIN
BURNER
Rp 1/2
Rp 3/4
Rp 3/4
Rp 3/4
75
85
70.000
Output
4
5
6
7
– Adjustment valve
8
M1 – Power supply pressure test point
M2 – Head pressure test point
Methane  80 kW and LPG
Methane and LPG
4
GB
3
3
(8,570 kcal/Nm
).
D5056
95
kW
80.000
kcal/h
8
M2
USE
D5069

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

567 m37567043756706

Tabla de contenido