INSTALLATION INSTRUCTIONS
CAUTION
• The drain pipes should be connected according to the installation manual for proper drainage.
• Insulate the drainpipes to prevent exterior condensation.
• Follow local plumbing codes when connecting drainpipes.
Requirements:
• All condensate drain lines should be insulated.
• Drain lines should have a minimum 1/4" per foot slope; avoid dips and sags.
• The developed length of the condensate drain line should be no greater than 65 feet, and support hangers should not be
spaced greater than 5 feet apart.
• The central piping should be connected according the following drawing.
• Follow the piping diagrams below for condensate drain piping.
4.9-6.6ft (1.5m~2m)
Heat
Down gradient
insulating
over 1/100
material
Piping Material
1-1/4 inch sch. 40 PVC
Insulating Material
1/4 inch thick Polyethylene wrap
Drain Hose:
Attach the soft end of the drain hose to the drain port with clamp. The hard end is 1-1/4 PVC. Use glue to attach
condensate drain line.
Eccentricity adjustment max 0.78in(20mm)
Insulation Wrap:
• Drain pipe needs to be insulated to prevent condensation
buildup and possible water damage.
Lifting Drainpipe:
• The drainpipe can be lifted no more than 24in (360mm).
31-5000473 Rev. 0
Support bracket
45° bending (max)
20
Pipe should drop 3.9in (10cm)
No waves or dips
Hose clamp
45°
Hose clamp
Water outlet
VP 30
Down gradient
over 1/100
Hose clamp
Hose
Hose
Indoor unit
Hose
PVC pipe
Rigid PVC
adhesive
13