NOTICE
This product is designed and rated for continuous operation at ambient temperatures up to 104°F(40°C). If
needed, this product can be operated at temperatures ranging from 5°F(15°C) - 122°F(50°C) for short periods.
If the product is exposed to temperatures outside of this range during storage, it should be brought back within
this range before operation. This product must always be operated outdoors in awell-ventilated area and far
away from doors, windows, and other vents.
Maximum wattage and current are subject to and limited by such factors as fuel BTU content, ambient
temperature, altitude, engine conditions, etc. Maximum power decreases about 3.5% for each 1,000 feet above
sea level, and will also decrease about 1% for each 10°F(6°C) above 60°F( 16°C) ambient temperature.
120V AC, 20A Duplex GFCI
Your generator is equipped with ground fault circuit interrupter (GFCI) receptacles. In the event of a ground fault,
a GFCI trips automatically to stop the flow of electricity and prevent serious injury. The LED Indicator Light on
the receptacle will be turn off. Press the "RESET" button located on the front of the receptacle to restore flow of
electricity. GFCI does NOT protect against circuit overloads. To ensure proper operation of the GFCI duplex,
perform this test monthly:
1. With the generator running, plug a test lamp into the GFCI receptacle. Turn the lamp on.
2. Press the "TEST" button located on the front of the receptacle to trip the device. This should immediately stop
the flow of electricity and shut off the lamp. If the electricity is not stopped, do not use this receptacle until it has
been serviced or replaced.
3. Press the "RESET" button located on the front of the receptacle to restore the flow of electricity. If the LED
Indicator Light does not come back or GFCI cannot be reset, then it must be replaced.
Receptacle
Outlet
LED Indicator Light
Reset Button
Test Button
Outlet
RESET
TEST