tRoublEShootINg chARtS
c. REFRIgERAtoR Not cold ENough
1
Flame properly adjusted?
2
Cooling element free from thick frost?
3
normal load of ice packs for freezing?
4
door closing properly?
5
Good air circulations inside and around the
refrigerator?
6
Refrigerator correctly levelled?
7
Condenser free from dust?
8
Flue baffle in position?
9
Refrigerator placed in coldest possible place?
10
better function on electricital operation?
11
Repeat start-up procedure on kerosene.
www.sibir.com
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
See "Troubleshooting charts > Kerosene
NO
operation > d. Aladdin burner" or "Troubleshoo-
ting charts > Kerosene operation > e. Kosmos
burner".
Turn out flame and defrost.
NO
Take some ice packs out.
NO
Check door gasket.
NO
Improve installation and rearrange vaccine.
NO
level refrigerator.
NO
Clean condenser.
NO
Hang flu baffle in position.
NO
Place it in a colder place.
NO
Replace the cooling unit.
NO