SCENE MANAGEMENT
A button can be used to activate a scene (short contact closure < 3 s) or memorise new
values (long contact closure, > 3 s).
In this mode the LED flashes briefly when transmitting the scene learning command.
Only one scene can be associated to each input.
THERMAL REGULATION COMMANDS
A switch is used to send commands towards the thermal regulation KNX/EIB devices,
such as for instance the thermostat on a heating system. Input can be configured to:
• enable (contact closed) or disable (contact open) the thermal regulation device;
• to set the thermal regulation device functions to one of the modes below:
closed contact
Comfort
Comfort
Economy
Frostprotect
An eventual status indicator LED is always OFF.
GENERAL DESCRIPTION
open contact
Economy
no action
no action
Auto