All manuals and user guides at all-guides.com
12
SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
Communication
Communication options for the SLC 5/03, 5/04, and 5/05 processors are as follows:
• DH485
• RS-232 protocols
(DF1 Full-Duplex, DF1 Half-Duplex "master/slave", DH-485, or ASCII)
• Data Highway Plus™
(A 1785-KA5 is required for the SLC 5/03 and SLC 5/05 processors.)
• Ethernet TCP/IP (SLC 5/05 only)
General Specifications
Description
Power Supply Loading at 5V dc
Power Supply Loading at 24V dc
Program Scan Hold-up Time after Loss of
Power
Noise Immunity
Vibration
Shock (operating)
Ambient Temperature Rating
Humidity
Agency Certification
Publication 1747-IN009A-ML-P
Specification
500 mA for the SLC 5/03 processor
1.0 A for the SLC 5/04 and 5/05 processors
175 mA for the SLC 5/03 processor
200 mA for the SLC 5/04 and 5/05 processors
20 ms to 3 s (dependent on power supply loading)
NEMA Standard ICS 2-230
Displacement: 0.015 inch, peak-to-peak at 5-57 Hz
Acceleration: 2.5Gs at 57-2000 Hz
30Gs
Operating: 0 to +60°C (+32°F to +140°F)
Storage: 40°C to +85°C (-40°F to +185°F)
5 to 95% without condensation
UL listed
CSA approved
Class 1, Groups A, B, C or D, Division 2
CE compliant for all applicable directives