All manuals and user guides at all-guides.com
SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
2. Set the communication parameters of the software to match the default
parameters of the processor:
Channel 0 Configuration
SLC 5/03, 5/04, 5/05
DF1 Full-Duplex:
• no handshaking
• 19.2K baud
• CRC Error Check
• duplicate detect on
• no parity

Replacing the Battery

Your SLC processor provides back-up power for RAM through a replaceable lithium
battery. This battery provides back-up for approximately 2 years. The BATT LED
on the front of the processor alerts you when the battery voltage has fallen below a
threshold level.
To replace the lithium battery follow these steps:
ATTENTION: Do not remove the processor from the SLC 500
chassis until all power is removed from the SLC 500 power supply
!
1. Remove power from the SLC 500 power supply.
2. Remove the processor from the chassis by pressing the retainer clips at both the
top and bottom of the module and slide it out.
ATTENTION: Do not expose the processor to surfaces or other
areas that may typically hold an electrostatic charge. Electrostatic
!
charges can alter or destroy memory.
3. Unplug the battery connector. Refer to the figure on page 10 for battery
connector location.
Channel 1 Configuration
SLC 5/03
DH-485:
• 19.2K baud
• node address = 1
SLC 5/04
DH+™:
• 57.6K baud
• node address = 1
Publication 1747-IN009A-ML-P
9
SLC 5/05
Ethernet

Publicidad