04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is OFF
Interface
07: Bypass voltage range setting
Interface
Segurança e harmonia
ININTERRUPTA
Setting
Parameter 3: Enable or disable ECO function.
You may choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable
Setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO
mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to
+24V of the nominal voltage.
LLS: Low loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V
of the nominal voltage.
Setting
Parameter 3: Enable or disable Bypass function.
You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable
Setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage
point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac.
LLS: Bypass low voltage point
For 208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to 220Vac
3. Operations
PH 9260
Uninterruptible Power Supply
EN
41