Firing Rates - Riello RS 100/M TC FS1 Instrucciones De Instalación, Montaje Y Funcionamiento

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical description of the burner
3
3.7
Firing rate
The maximum output is chosen within area A of the diagram.
The minimum output must not be lower than the minimum limit of the diagram.
Warning
The firing rate was obtained considering an ambient temperature of 20°C and an atmospheric pressure of 1013 mbar (approx. 0 m
above sea level), with the combustion head adjusted as shown in Ch. 4.6.
Fig. 4
20133205
Burner output
The firing rates were obtained in special
test boilers, according to EN 676 regula-
tions.
Fig. 4 indicates the diameter and length of
the test combustion chamber.
Example
D715
Output 756 kW (650 Mcal/h):
diameter 60 cm,
length 2m.
The coupling is ensured when the boiler is EC
type-approved; for boilers or ovens with com-
bustion chambers of very different dimensions
compared to those shown in the diagram of
Fig. 4, preliminary checks are recommended.
8
GB
20094745
Fig. 3