Descargar Imprimir esta página

Water Flow Setting - Hayward 81504 Manual De Instalación E Instrucciones

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 64
4. USER INTERFACE (continued)

4.5 Water flow setting

While the heat pump is running and the water inlet and outlet valves are open,
adjust the by-pass valve to obtain a difference of 2°C between the water
inflow and outflow temperature (see Functional Diagram Section 3.1).
You can check the setting by viewing the inflow and outflow temperatures
directly on the control panel by following the procedure below.
Inflow
temperature
5 s
Then adjust the by-pass to obtain a difference of 2°C between the inflow and
the outflow.
Press
once to exit the menu.
Note: Opening the by-pass valve creates a weaker flow which results in an
increased ∆T.
Closing the by-pass valve creates a stronger flow which results in a
decreased ∆T.
Outflow
temperature
10 s
15

Publicidad

loading

Este manual también es adecuado para:

81514815248153481544