Connecting IntelliChlor
To connect the four wire communication cable from the IntelliChlor SCG Power Center (see page 27) to the
motherboard located in the SunTouch
WARNING - Switch OFF main system power to the Load Center before making any connections.
To access the Power Center electronics compartment:
1. Unlatch the front door of the Power Center, and open the door.
2. Loosen the retaining screw on front panel. Open the hinged front panel to access the electronics
compartment.
3. Route the four conductor cable up through the Power Center grommet opening located on the left
side, and up through the low voltage raceway to the motherboard.
4. Strip back the cable conductors 1-1/4 in. Insert the wires into the screw terminals (provided in the
kit). Secure the wires with the screws. Make sure to match the color coding of the wires:
Red = +15, Yellow = +DT, Green = -DT, and GND = Black.
5. Insert the connector on the COM-PORT (J11) screw terminal on the motherboard.
6. When the connection is completed, close the control panel and secure it with the retaining screw.
7. Close the front door. Fasten the spring latch.
COM PORT
Wiring AC Power from IntelliChlor (SCG) and IntelliFlo
®
IntelliTouch
, EasyTouch
(see page 27 for diagram)
IntelliChlor (SCG) AC Wiring Instructions: When using the IntelliChlor SCG and an IntelliFlo pump
(or 2-speed pump) with an IntelliTouch, EasyTouch or SunTouch Control System, the IntelliChlor AC
power center wires must be connected to the LOAD SIDE OF THE FILTER PUMP RELAY located in the
Load/Power Center (see diagram on page 27). This ensures that the IntelliChlor SCG cell produces
chlorine only when the main filter pump is on. This method does not require a ground fault circuit-
interrupter (GFCI) to protect the circuit. Note: For non-automation control systems using a time clock,
see page 30 for wiring information.
®
IntelliChlor
Salt Chlorine Generator Installation and User's Guide
®
SCG to an SunTouch
®
Control System Power Center:
GAS
HEATER
RESET
SunTouch Control System
motherboard
®
and SunTouch
®
Control System
CLNR
®
pump to
®
Control System