Descargar Imprimir esta página

Beninca CBY.24V Manual De Instrucciones página 6

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 9
CBY.24V
Battery charger card for the connection of emergency batteries to control units for 24VDC motors.
Either lead batteries or NiMh batteries can be used:
- Connection to lead batteries model DA.BT2/DA.BT6
Figure 1 shows the connection of lead, 12V batteries. Terminal NTC must not be connected.
- Connection of NiMh batteries
Figure 2 shows the connection of NiMh, 24Vbatteries.
IMPORTANT: The rapid connector of NiMh should be cut. Cut one wire at a time to avert any short-circuits.
Connect the three wire while respecting the colours:
Red: +/Black: - /Blue: NTC (thermal sensor).
As regards the connection to the control unit, 3 different ways are available, according to the type of control unit:
- Control unit with rapid connector for battery charger:
If the control unit is provided with a rapid connector for the battery charger, it is sufficient to connect the two connectors with the cable supplied,
as shown in Figure 3.
NOTE: Some control units are provided with rapid connectors for other uses, e.g. radio receivers.
Before proceeding to the wire connection, check on the user's manual supplied with the control unit that the rapid connector is actually supplied
for battery chargers.
- Control unit with 0V/24V inputs:
If the control unit is connected to the transformer through only two connections (0V/24V), disconnect the transformer and, after removing the terminal
cover, carry out the wire connections as shown in Figure 4. Terminals VMTRS and 24 TRS should be short-circuited.
- Control unit with 0V/24V inputs and motor speed input:
Some 24V control units are equipped with an additional wire connection which regulates the motor speed to the various values available in the
transformer.
In this case, disconnect the transformer and, after removing the terminal cover, carry out the wiring as shown in Figure 5.
The following table describes the terminal board in detail.
During operation, should a power failure occur, the 24V accessory output of the control unit is polarised.
It is mandatory to check the correct operation of accessories, as described in the user's manual of the control unit.
Input/Output functions
+
+ 24VDC from the emergency battery
-
- 24VDC from the emergency battery
NTC
Thermal sensor (for NiMh batteries)
0sc
Connect to 0V connector of the control unit
0trs
Connect to 0V secondary terminal of the transformer
Connect to the 24V secondary terminal of the transformer
24trs
(from 23 to 28VAC).
Connect to secondary terminal of the transformer (23V
min.).
VMtrs
CAUTION!: Select the motor operating speed. To perform a
correct connection, make reference to instructions of the
control unit.
VMsc
Connect to the Vmot connector of the control unit
24sc
Connect to the VAux of the control unit.
The board features two LEDs that indicate the status of the system:
CHARGER STATUS
Normal operation - battery not charging
Battery charging
Battery Operation
Battery operation (with battery and load disconnected)
Check battery disconnected
NiMh battery in thermal protection
During the normal network powering, the card maintains the battery charged.
If a power failure occurs, the card powers the system through the batteries. A F10A fuse protects the control unit during operation with the emergency
battery.
The buffer battery operates until 18V is reached. The charge is reduced progressively. When this value is reached, the battery is disconnected.
6
ENGLISH
CAUTION!
Charge current
Charge voltage
Charge time
(for 2Ah batteries)
Diagnostics
GREEN LED
Continuous flashing
On
Fast blinking
1 short blink with pause
Fast blinking
On
Notes.
Specification:
27.2 VDC
27,2 Vdc
10 ore circa
RED LED
Off
On
Off
1 short blink with pause
Fast blinking
Fast blinking

Publicidad

loading