Descargar Imprimir esta página

Precautions Regarding Electromagnetic Disturbance Generated By The Appliance - Cristec YPOWER 12V-12V/60A Manual Del Usuario

Publicidad

Idiomas disponibles

Idiomas disponibles

For battery cables up to 3 metres, the cross-section of the battery cables should be at least equal to or greater than the
values provided in the table below:
0V common (Output +12V or Input +12V)
The installer should choose the type of cable (H07-VK, MX, etc.) according to the type of application and the applicable
standards. The connection is made by bolting ring terminals to the 3 electrical power studs.
Input
0V common
Output
3.2.2

Precautions regarding electromagnetic disturbance generated by the appliance

We recommend a minimum distance of 2m between the charger / converter and any potentially sensitive equipment.
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the receiving
ends.
Keep cable length and shielding connections to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should be placed
against the hull or walls).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any deviation to power another appliance is prohibited.
(
)
*
This is a recommendation for installation rather than an obligation. The installing electrician should decide whether or not
to use shielded cable depending on the EMC environment.
Cable
0V common (Other configuration)
Input +12V
Input +24V +36V + 48V
Output +12V
Output +24V +36V + 48V
Battery cable cross-section
25mm²
10mm²
25mm²
10mm²
25mm²
10mm²
35

Publicidad

loading