In programming mode, the number of flashes of LED "ON" gives the programming field, the number of flashes of the
green LED "FLOATING/REFRESH" gives the programming value.
Example: field 3 , N = 5
Led "ON"
Led "FLOATING/REFRESH"
3.3.2
Programming field 1 : Select type of batteries
Configuration according to type of batteries 12V or 24V or 36V or 48V
Setting
0
1
2
3
4
5
6
7
8
9
10
11
Description of the battery type
Opened type bat
free electrolyte (wet)
Classic sealed type bat
(Sealed lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby sealed
bat
Stabilized DC power supply
SPE1 open type bat
Lithium iron phosphate
(LiFePO4) with BMS(***)
STORMLINE Bat
Specific
FLOAT voltage
BOOST voltage
12V/24V
12V/24V
36V/48V
36V/48V
13.4V/26.8V
14.1V/28.2V
40.2V/53.6V
43.2V/56.4V
13.8V/27.6V
14.4V/28.8V
41.4V/55.2V
43.2V/57.6V
13.8V/27.6V
14.4V/28.8V
41.4V/55.2V
43.2V/57.6V
13.6V/27.2V
14.4V/28.8V
40.8V/54.4V
43.2V/57.6V
13.6V/27.2V
14.4V/28.8V
40.8V/54.4V
43.2V/57.6V
14.4V/28.8V
15.1V/30.2V
43.2V/57.4V
45.3V/60.4V
13.4V/26.8V
13.4V/26.8V
40.2V/57.6V
40.2V/57.6V
12V/24V
12V/24V
36V/48V
36V/48V
13.2V/26.4V
14.8V/29.6V
39.6V/52.8V
45.4V/59.2V
13.8V/27.6V
14.4V/28.8V
41.4V/55.2V
43.2V/57.6V
13.7V/27.4V
14.5V/29V
41.1V/57.8V
43.5V/58V
12V/24V
12V/24V
36V/48V
36V/48V
Maximum
Maximum
duration
duration
of BOOST
of ABSOPTION
at +/- 5% T
at +/- 5% T
BOOST
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
0H
0H
0H
0H
2H
4H
6H
1H
2H
6H
0H
0H
ABS
37