INSTALLATION INSTRUCTIONS
C-FL-A-FLW Series
MOUNTING USING 2" ADJUSTABLE FITTER
NOTE: Fixture is intended to be mounted on 2-3/8" (60 mm) O.D.
heavy wall pipe or tenon.
1.
Remove (2) screws holding fitter cover in place. Remove fitter
cover to expose splice chamber of fitter.
2.
Route supply leads through end of mounting pipe or tenon,
through open end of fitter, and into splice compartment of fitter.
3.
Slip lower fitter over pipe or tenon, being careful not to pinch any
leads.
4.
Strain relief is required for electrical connections in 2" adjustable
fitter mounts at heights of 25' (7.6 m) and above. Tie a knot in the
supply wires above the hole form the lower fitter into the splice
chamber to reduce the strain on the connections. Make sure the
knot will not slip through the hole.
5.
Aim fixture by rotating on pipe or tenon to desired direction.
Securely tighten (2) Allen head set screws on fitter to 140 in-lbs
(16 N-m).
6.
See Wattage and Color Temperature Settings section to set
wattage and CCT.
7.
Wire as indicated in Electrical Connections section.
8.
Loosen (DO NOT REMOVE) the bolt holding the two halves of the
fitter together. Tilt fixture to desired angle and re-tighten bolt to 19
ft-lbs (25 N-m).
9.
Carefully tuck all leads and splices into splice chamber and
replace cover. Re-tighten screws to 25 in-lbs (3 N-m).
WATTAGE AND COLOR TEMPERATURE SETTINGS
NOTE: Factory Settings Are 100% Wattage And 4000K.
1.
Remove the selector switch cap on the side of the fixture housing
using a large straight blade screwdriver. See Figure 2.
2.
Locate the selector switches under the cap and select wattage and
color temperature by sliding the dip switches to the desired values.
3.
Replace the selector switch cap and retighten using a large
straight blade screwdriver.
FIGURE 2
Selector Switch Cap
http://lighting.cree.com/warranty
Document:
LPN00872X0001A0_A
Created By:
TMT
FCC NOTICE
CAUTION: Changes or modifications not expressly approved could void
your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-003 (A)/NMB-003 (A)
ELECTRICAL CONNECTIONS
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green or
bare copper) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green or
bare copper) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
|