OvERlOAD INDICATOR lIGhT (RED)
The overload indicator light 1 comes on when an overload
of a connected electrical device is detected, the inverter
control unit overheats, or the AC
output voltage rises. Then, the AC protector will trip, stop-
ping power generation in order to protect the generator and
any connected electric devices. The AC pilot light (Green)
will go off and the overload indicator light (Red) will stay
on, but the engine will not stop running.
When the overload indicator light comes on and power generation stops, proceed as follows:
1. Turn off any connected electric devices and stop the engine.
2. Reduce the total wattage of connected electric devices within the rated output.
3. Check for blockages in the cooling air inlet and around the control unit. If any blockages are found, remove.
4. After checking, restart the engine
TIP: The overload indicator light may come on for a few seconds at first when using electric devices that require a large
starting current, such as a compressor or a submergible pump. However, this is not a malfunction.