Descargar Imprimir esta página

Klein Tools CL120KIT Manual De Instrucciones página 7

Publicidad

Idiomas disponibles

Idiomas disponibles

ENGLISH
MAINTENANCE
BATTERY REPLACEMENT
When
indicator is displayed on LCD, batteries must be replaced.
1. Loosen captive screw and remove battery cover.
2. Replace 3 x AAA batteries (note proper polarity).
3. Replace battery cover and fasten screw securely.
Replace battery cover and fasten screw securely.
To avoid risk of electric
To avoid risk of electric
shock, disconnect leads from
shock, disconnect leads from
any voltage source before
any voltage source before
removing battery door.
To avoid risk of electric
To avoid risk of electric
shock, do not operate meter
shock, do not operate meter
while battery door is removed.
while battery door is removed.
Be sure meter is turned off and wipe with a clean, dry lint-free
cloth. Do not use abrasive cleaners or solvents.
Remove the batteries when meter is not in use for a prolonged
period of time. Do not expose to high temperatures or humidity.
After a period of storage in extreme conditions exceeding the limits
mentioned in the General Specifications section, allow the meter to
return to normal operating conditions before using.
WARRANTY
www.kleintools.com/warranty
DISPOSAL / RECYCLE
Do not place equipment and its accessories in the trash.
Items must be properly disposed of in accordance with local
regulations. Please see www.epa.gov/recycle for additional
information.
CUSTOMER SERVICE
KLEIN TOOLS, INC.
450 Bond Street Lincolnshire, IL 60069 1-800-553-4676
customerservice@kleintools.com
12
CLEANING
STORAGE
www.kleintools.com
GENERAL SPECIFICATIONS
Relative Humidity: < 85% non-condensing
Operating Temperature: 32° to 140°F (0° to 40°C)
Storage Temperature: 14° to 122°F (-10°C to 50°C)
Weight: 1.3 oz. (37 g)
Nominal Power: 0.3W
Certifi cation: Conforms To UL Std 1436
Certified To CSA Std C22.2 # 160
Drop Protection: 6.6 ft. (2 m)
Nominal Voltage: 110/125V AC at 50/60Hz in 3-wire outlet
Read, understand, and follow all warnings and instructions before
operating testers. Failure to follow instructions could result in
death or serious injury.
• Before each use, verify tester operation by testing on a known live
and correctly wired receptacle.
• Do not use if the tester appears damaged in any way.
• The tester is intended for indoor use only.
• Other equipment or devices attached to the circuit being tested
could interfere with the tester; clear the circuit before testing.
• This tester only detects common wiring problems. Always consult
a qualified electrician to resolve wiring problems.
FIG. 1
Indicator Illuminated
RED
YELLOW
INDICATOR
FAULT
Open Ground
Open Neutral
Open Hot
Hot/Ground Reversed
Hot/Neutral Reversed
Correct
Neutral (White)
RT210
WARNINGS
Indicator Not Illuminated
EXPLANATION
Ground contact is not connected
Neutral contact is not connected
Hot contact is not connected
Hot and ground connections are reversed
Hot and neutral connections are reversed
Receptacle is wired correctly
Hot (Black)
Ground (Green)
13

Publicidad

loading