LG PREMTA200.ENCXLUS Manual De Instalación Del Usuario página 22

Control remoto con cable

Publicidad

Idiomas disponibles

Idiomas disponibles

22 SETTINGS
Product
Function
Aircon Vent.
Outdoor Unit
Refrigerant
This function sets the refrigerant noise
O
O
Noise
reduction mode of the outdoor unit.
Reduction
This function improves operation
Smart Load
efficiency based on indoor, outdoor
O
O
Control
temperature and humidity values.
Set SLC step value.
This function sets the defrost mode
Defrost Mode
O
O
operation of the outdoor unit.
Low Noise
The product will operate in quiet mode
O
O
Mode Time
for the set time.
It is a function to create a pleasant
Advanced
indoor environment, the fan speed
Fan Speed
O
is automatically adjusted according
"Auto"
to the difference in indoor/desired
temperature.
After a delay for the set-up time, the
Delay Time
O
ventilation system operates.
You can save energy by releasing
Midnight Air
O
indoor heat at night in summer and
Cooling
supplying cool outdoor air to indoor.
This function remembers the desired
My Favorite
temperature that the user frequently
O
Temperature
sets and automatically sets it during the
initial operation.
This function sets the FAN operating
CO
Fan
2
O
standards based on the CO2
Control
concentration of ventilation products.
Energy saving can be achieved
Human
through power saving operation and
Detection
O
wind direction setting through human
Mode
sensing.
Top And
This function sets the use of the upper
Bottom
O
and lower vanes when operating the
Selection
product.
Provides outside air to a room to save
Economizer
O
energy and improve the air quality
indoors
Indoor Unit
This function adjusts the brightness of
Display Light
O
the indoor unit display light.
Brightness
NOTE
• Depending on the product, some functions may not work.
Description
This function is available only if the outdoor unit Master / Slave setting of the
installer settings is Master.
Set the Start time / End time. It is only possible to set when the outdoor unit
M/S setting of the installer setting is Master and the outdoor unit low noise
mode priority setting is "Remote controller".
On / Off
5 / 10 / 15 / 20 / 25 min
Enter the midnight air cooling only when the set time is satisfied with the
outdoor temperature conditions.
On / Off
On/Off Control : In absence,
operation stops after occupancy
Temp. Control : When absent, it
controls the desired temperature to
perform a power saving function.
Both Open / Upper Vane Open / Lower Vane Open
Disable the
economizer function
to keep the outside
air damper closed.
When the indoor
unit is running, turn
on the indoor unit
display light.
Option
Fan Control During
Operation On
Off / Low / Periodic
Saving Operation
maintenance time is set.
Off : function unused
Off
Auto
If the outside air
temperature is
lower than the
air temperature
indoors when
cooling is being
operated, outside
air is supplied to
the room to save
energy.
On
Off
"Off" setting is
only available
in the indoor
units that have
brightness control
function.
Fan Control During Operation Off
Off / Periodic
Time
5/10/15/30/60 min
Step 1
Step 2
Opens the
Opens the outside
outside air
air damper opening
damper opening
by one stage to
by two stages
improve the indoor
to improve the
air quality by
indoor air quality
introducing fresh air
by introducing
into the room.
fresh air into the
room.
Auto
"Auto" setting is only available in the
indoor units that is equipped with the
human detection sensor.When set
to Auto, the indoor unit display light
brightness will automatically adjust
according to the illuminance detected
by the human detection sensor.