TECHNICAL DATA

Hazardous and Environmental Ratings
Control
Station
Cover
Back Box
Operator(s) Hazardous Ratings
Cl. I, Div. 1 & 2, Gr. C,D
Cl. I, Div. 2, Gr. B
EDS/EDSC
EDS
All DEVX
Cl. I, Zones 1 & 2, IIA
EFS
EFS/EFSC
Cl. I, Zone 2, IIB+H2
DSD
Cl. II, Gr. E,F,G; Cl. III
Cl. I, Div. 1 & 2, Gr. B,C,D
All DEVX
Cl. I, Zone 1 & 2, IIA,
except
EFS
EFS/EFSC
DEVX30
IIB+H2
models
Cl. II, Gr. E,F,G; Cl. III
Cl. I, Div. 2, Gr. B,C,D
EDSX
DSDX
EDS/EDSC
All DEVX
Cl. I, Zone 2, IIA, IIB+H2
Cl. II, Gr. E,F,G; Cl.III
*Seals are not required for Class I, Division 2.
**Only for single gang back boxes. Iron back boxes require "X" on conduit hub. No marking required for aluminum back boxes. Cannot be used with GB suffix.
***NEMA 4X only for aluminum back boxes. Iron back boxes limited to NEMA 4.
Electrical Ratings
ESWP126*
1 N.O. and 1 N.C. Contact
10A, 600VAC, A600, P150
DEVX30
120V, 6W
DEVX30 LED
120V, 1.2W
DEVX30 S300
24V, 1.7W
DEVX30 LED S300
24V, .2-.6W
DEVX30 Gray Wire Connector
300V
DEVX30 Gray Wire Connector
600V
DEVX30 T2
240/120V Transformer
DEVX30 T4
480/120V Transformer
DEVX30 T5
600/120V Transformer
*Used on all DEVX operators except DEVX30 pilot lights
Agency Certifications
NEC
UL1203, UL121201, UL508
CEC
CSA C22.2 Nos. 14, 25, 213-17
Torques in.-lbs. (N-m)
DEVX Operators
1/2 ± 1/4 Turns*
ESWP126 Contact Block Terminals
15 (1.7)
ESWP Contact Block Mounting Screws
2.1 (0.24)
Mounting Block Set Screw
10 (1.2)
Double Contact Block Actuator Screw
9 (1.0)
Mounting Plate Screws
5 (0.6)
Handle Cap Screw
5 (0.6)
Cam Module Mounting Screws
10 (1.2)
Push Button Screws
10 (1.2)
Guard Screws
8 (0.9)
Transformer Screw
5 (0.6)
Cover Screws
60 (6.8)
Ground Screw
18 (2.0)
*Torque turns start when gasket(s) initially begin to compress.
IF 899 • 12/21
Copyright © 2021, Eaton's Crouse-Hinds Division
Standard
Standard
Conduit Seal
Extended
Environ.
Temperature
Requirements
Temp.
Ratings
Ratings
(Cl. I, Div. 1)*
Range**
None
Within 1.5" for
EDS w/ GB Suffix
-50°C to
NEMA 3
-25°C to +40°C
+60°C
None for 1/2" or
3/4" Hub Size
Within 5 ft. on 1"
Hub Size
NEMA
4X***
-40°C to +60°C None
N/A
IP66
All DEVX
All DEVX Except DEVX30 Pilot Lights
All DEVX Except DEVX30 Pilot Lights
All DEVX
All DEVX12
All DEVX12
All DEVX42/43/44 Except S847
Option
All DEVX42/43/44
DEVX22
DEVX22
DEVX30 T2, T4 or T5
All Enclosures
All Enclosures
Weights lbs. (kg.)
Single Gang EDS(X) + (2) Device
Extended Temp.
Range Conduit
Double Gang EDS(X) + (4) Device
Seal Req.
(Cl. I, Div. 1)*
Single Gang EDS + (2) Device
Double Gang EDS + (4) Device
Within 1.5"
Not allowed for
EDS w/ GB Suffix
Replacement Parts
Description
Single Gang Flange Gasket
Within 18"
Captive Cover Screw
Regular Cover Screw
N/A
Long Cover Screw
ESWP126 Contact Block
Operator Gasket
Legend Plate Gasket
DS(X) Cover
EDS, EDSC Back Box
EFS, EFSC Back Box
DEVX
ESWP126
Legend Plate
110-125 Volt Circuit: 6 Watt, T21/2 Miniature Bayonet Base
LED Replacement: 24, 120VAC, T31/4 Miniature Bayonet Base
Wire Range AWG
ESWP126 Contact Block
12-22
1 #14
1 or 2 #16
1 #18 stranded
DEVX30 Gray Wire
2 or 3 #18
Connectors
2 or 4 #20
300V
2 #22 stranded
3 or 4 #22
5 #22 solid
1 or 2 #14
1 #16 stranded
2 #16
1 #18 stranded
DEVX30 Orange Wire
Connectors
600V
2 or 4 #18
1 #14 w/1 or 2 #18
1 #14 w/1 to 3 #20
1 #14 w/1 to 3 #22
Size wire based on application
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed.
In accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product
for his intended use and assumes all risk and liability whatsoever in connection therewith.
Page 3
Aluminum Cover & Back Box
4.7 (2.1)
Aluminum Cover & Back Box
8.8 (4.0)
Iron Cover & Back Box
9.9 (4.5)
Iron Cover & Back Box
19.2 (8.7)
Catalog Number
Used On
EDSX K1
DSDX/EDSX
EDSX K2
DSDX/EDSX
EDS K1
EDS, DSD w/ EDS Back Box
EDS K2
EFS, DSD w/ EFS Back Box
ESWP126
DEVX
DEVX K1
DEVX
DEVX K2
DEVX
See Catalog
ALL
See Catalog
ALL
See Catalog
ALL
See Catalog
ALL
See Catalog
ALL
See Catalog
ALL
1 #14 w/1 #20 or #22
2 #18 w/1 #20
1 #16 w/1 #18
2 #18 w/1 or 2 #22
1 #16 w/1 or 2 #20
1 #20 w/1 to 4 #22
1 #16 w/1 to 3 #22
2 #20 w/1 to 3 #22
1 #16 w/1 #20 w/1 #18 or #20
3 #20 w/1 or 2 #22
1 #18 w/1 to 3 #20
4 #20 w/1 #22
1 #18 w/1 to 4 #22
1 or 2 #18 w/1 #20 w/1 #22
1 #14 w/1 #16 w/1 #18
1 #16 w/1 #18 w/1 #22
1 #14 w/1 #16
1 #18 w/2 to 4 #20
1 #16 w/1 or 2 #18
1 #18 w/ 3 or 4 #22
1 #16 w/1 to 3 #20 or #22
1 or 2 #18 w/1 #20
w/1 #22
2 #16 w/1 or 2 #20
2 #18 w/1 or 2 #20
2 #16 w/1 to 3 #22
2#18 w/1 to 3 #22
2 #16 w/1 #18
3 #18 w/1 #20 or #22
1 or 2 #16 w/1 #20 w/1 #22