CLEARANCE TO COMBUSTIBLES
(Refer to Figure 1 and Table 1)
The following stated clearances represent the minimum
distances between the stove and any other object. No
objects should encroach into this space. This includes
but is not limited to carpet, furniture, children, pets,
clothing, fuel, or any other object. These clearances
may not be reduced by any means or regulatory
authority within United States or Canada.
The stove shall not be less than 20 inches (51 cm)
(A) from a side wall and [U.S. - 8.25 inches (21 cm);
Canada - 12.25 inches (31 cm)] (B) from the back wall.
The wall of a vertical vent pipe must not be less than
26.75 inches (68 cm) (C) from any wall.
The Minimum floor-to-ceiling distance of the room is
84 inches (213.4 cm).
The minimum distance between the ceiling and the
wall of any horizontal vent pipe is 18 inches (45.7 cm).
REAR WALL
G
G
E
A
C
USA
A 20 in. (51 cm)
B 8.25 in. (21 cm)
C 26.75 in. (68 cm)
D 14 in. (35.6 cm)
E 8 in. (20.3 cm)
F 16 in. (40.6 cm)
G 2 in. (5.1 cm)
H 6.5 in. (16.5 cm)
I
16 in. (40.6 cm)
Wood Fire Stove
FIGURE 1
E
FRONT OF STOVE
NON-COMBUSTIBLE
FLOOR PROTECTION
CANADA
20 in. (51 cm)
12.25 in. (31 cm)
26.75 in. (68 cm)
18 in. (45.8 cm)
8 in. (20.3 cm)
18 in. (45.7 cm)
2 in. (5.1 cm)
8.5 in. (21.6 cm)
18 in. (45.8 cm)
Table 1
CORNER INSTALLATION
The stove shall not be less than [U.S. - 6.5 inches (16.5
cm); Canada - 8.5 inches (21.6 cm)] (H) from a corner.
The wall of a vertical vent pipe must not be less than
[U.S. - 16 inches (40.6 cm); Canada - 18 inches (45.8
cm)] (I) from any corner.
FLOORING SPACE (Refer to Figure 1 and Table 1)
The floor protector must extend at least [in U.S. - 16
in. (40.6 cm); in Canada - 18 in. (45.7 cm)] (F) to the
front and at least 8 in. (20.3 cm) (E) beyond each side
of the fuel loading and ash removal opening. The floor
protection must extend under the flue connector and
extend 2 in. (5.1 cm) (G) beyond each side of the pipe.
FLOORING MATERIAL
The stove may be installed on solid concrete or solid
masonry flooring.
A combustible floor must be
protected with non-insulated ember board per CSA
B365. Space heaters meeting the requirements of CAN/
ULC-S627 are suitable for installation on a combustible
floor and do not require radiant floor protection.
ACCESSORY INSTALLATION
BLOWER KIT
(F500308)
The blower may be mounted to the rear of the stove.
When plugged in and while the stove is in use this
blower will propagate air along the outside of the fire
box, warming the air before it is then circulated into
the area to be heated. Check inside the stove to find
the blower contained in protective packaging.
WARNING: BLOWER MUST BE
DISCONNECTED FROM POWER SUPPLY
BEFORE INSTALLING. IT IS ONLY INTENDED
FOR USE WITH THIS STOVE.
Using a 5/16" open end or socket wrench, remove the
4 screws holding the rear panel. Attach the blower
mounting box to the rear of the unit using 4 of the
supplied #10 screws. Mount the blower assembly to
the mounting box with the 4 remaining #10 screws.
E5
Operating Instructions and Owner's Manual
FIGURE 2
I
H