Connection
The module connectors, DIP switch, and status LED are
shown in Figure 1:
1.
Earth screw
2.
Loop connectors
3.
Auxiliary power supply connectors
4.
Relay output connectors (C, NC, NO)
5.
DIP switch
6.
Status LED
Loop overloading
Always verify large installations using a loop load calculator to
confirm that enough power is available on the loop.
Note:
To avoid loop overloading when using loop-powered
devices, see the system installation and configuration
guidelines in the Loop Power and I/O Modules Application
Note. This document is available from your local distributor.
Power supply configuration
To set the module power supply, remove the unit cover and
configure jumpers JMP1 and JMP2.
Loop powered jumper
configuration.
WARNING:
Do not connect a 24 VDC auxiliary power supply
to the module if power is supplied by the loop
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status-LED (Figure 1, item 6) is configured using DIP
switch 8:
•
If set to ON the LED will flash during all communications
between the module and the control panel.
•
If set to OFF it will flash only during selected
communications between the module and control panel
(see control panel manual for further details).
The status LED is lit constantly during alarm.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry. To test the module:
1.
Configure the module as an output to be activated by a
detector or manual call point.
2.
Remove a detector head from its base or activate a
manual call point.
3.
If the status-LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
2 / 20
24 VDC auxiliary power supply
jumper configuration.
Specifications
Operating voltage
Relay contact rating
Max.switching voltage
Nominal current
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions
Current consumption (externally powered)
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
Current consumption
24 VDC aux. supply (standby)
24 VDC aux. supply (alarm)
Current consumption (loop powered)
Loop current consumption
Standby
Alarm
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
0370
Declaration of
360-4109-0799
Performance number
Year of first CE marking
08
Product identification
KAL730
Intended use
See the product Declaration of Performance
Declared performance
See the product Declaration of Performance
Manufacturer
Carrier Manufacturing Poland Spòlka Z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland.
Authorized EU manufacturing
representative: Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste in
the European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
recyclethis.info.
22 to 38 VDC
AC: 42 V peak / DC: 30 V
AC: 0.5 A / DC: 0.5 A
−10 to +50ºC
−10 to +70ºC
10 to 95% (non condensing)
370 g
182 × 142 × 77 mm
70 µA
100 µA
<3.5 mA
22 mA
<50 mA
350 µA
<3.4 mA