Installation - Vortice Vort Ariasalus Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

ENGLISH

Installation

Installation diagram
2
Indoor
Grid with wind and
bird protection
Gradient
(1/100~1/50)
(Outdoor Fresh Air)
Mounting the appliance
False ceiling
The device must not be installed in areas where temperatures may fall below 0°C.
Install 4 M10 screws/bolts (not supplied), ensuring that the distance between the screws matches the distance
of the holes on the suspension kit:
3
4
Ceiling Suspension
Roof
Bolt
Access Door
Attic (on the floor)
4a
16
Outdoor
Thermal Insulation Material
(Insulation Adaptor and Aluminum Tape)
Fresh Air Supply Duct
Insulated duct
Hoop, Scotch tape
Nut
Washer
Ceiling Suspension
Fixture
Decorative
Ceiling
Noise Attenuator Φ80
Noise Attenuator (optional)
Hoop, Scotch tape
Mod
Vort Ariasalus
Keep a portion on the ceiling free for access to the
device in case of maintenance (dimensions as in the
following table):
Mod
Vort Ariasalus
Prepare the length of the bolt on the ceiling so that there
is a gap of at least 25 mm between the bottom of the
device and the upper side of the false ceiling. Similarly,
there must be a space of at least 20 mm between the
top of the device and the ceiling.
Install the suspension kit using 4 bolts:
- Make sure that the direction of the device is correct;
do not install the appliance upside down. Securely
fasten nuts and washers
- Make sure that the device is perfectly horizontal.
- The device must be easily accessible for maintenance
operations. In particular, the false ceiling into which it
is installed must have a suitably sized opening, which
must allow access to the openings of the device.
On the wall (vertical)
4b
flexible aluminum/PVC tube
S A
Supply Air
nozzle
S A
Supply Air
nozzle
C
D
[
[
mm]
mm]
540
440
A
B
[
[
mm]
mm]
330
550

Publicidad

Tabla de contenido
loading

Tabla de contenido