Jandy
Variable-Speed Pumps
®
MINIMUM WIRE SIZE AND MINIMUM OVERCURRENT PROTECTION*
Distance from Sub-Panel
Inverse - Time Circuit Breaker
or Branch Fuse AMPs
Pump Model
Class: CC, G, H, J, K, RK, or T
230 VAC
VSFHP185DV2A(S)
VSFHP270DV2A(S)
VSPHP270DV2A(S)
15A
VSSHP220DV2A(S)
VSSHP270DV2A(S)
*Assumes three (3) copper conductors in a buried conduit and 3% maximum voltage loss in branch circuit. All National Electrical Code
local codes must be followed. Table shows minimum wire size and branch fuse recommendations for a typical installation per NEC.
Suction
Base
Side
Configuration
Height
1. Pump without
7 3/4"
Base
2. Pump with
8 7/8"
Base
3. Pump with
9 1/8"
Base and Spacers
4. Pump with
10 3/4"
Small + Large
Base
Table 2.
Adjustable Base Dimensions
(VS FloPro
TM
1.
Using a hand cutter tool, cut the plastic bars
connecting the top and bottom sets of spacers, as
shown in Figure 6.
2.
Push the two top spacers and two bottom spacers
out of the base.
3.
Align the pins in the four spacers with the holes in
the base. Snap the spacers into place (Fig. 7).
Figure 6.
Cut Sets of Spacers Out of Base
|
Installation & Operation Manual
0-50 feet (15 meters)
115 VAC
230 VAC
14 AWG
20A
(2.1mm
Basket
SpeedSet
Lid
Controller
Height
Height
12 3/4"
14 1/8"
13 7/8"
15 1/4"
14 1/8"
15 1/2"
15 3/4"
17 1/8"
Models Only)
Cut
spacers
at X.
50-100 feet (15-30 meters)
Voltage
Voltage
115 VAC
230 VAC
12 AWG
12 AWG
)
(3.3mm
)
(3.3mm
)
2
2
2
Figure 7.
Snap Spacers into Place
3.3
Electrical Installation
3.3.1
Voltage Checks
The correct voltage, as specified on the pump data plate,
is necessary for proper performance and long motor
life. Incorrect voltage will decrease the pump's ability to
perform and could cause overheating, reduce the motor life,
and result in higher electric bills.
It is the responsibility of the electrical installer to provide
data plate operating voltage to the pump by ensuring
proper circuit sizes and wire sizes for this specific
application.
The National Electrical Code
requires all pool pump circuits be protected with a
Ground Fault Interrupter (GFCI). Therefore, it is also
the responsibility of the electrical installer to ensure that
the pump circuit is in compliance with this and all other
applicable requirements of the National Electrical Code
(NEC) and any other applicable installation codes.
All variable-speed pumps, regardless of brand, make
or model, are prone to create nuisance trips on GFCI
breakers. Siemens
are highly recommended to minimize or eliminate these
occurrences and offer 5 milliamp personal protection
while meeting 2008 to current NEC standards for pool
pumps.
ENGLISH
100-200 feet (30-60 meters)
Voltage
115 VAC
230 VAC
10 AWG
10 AWG
(5.3mm
)
(5.3mm
)
2
2
(NEC
, NFPA-70
®
®
QFP or QF series GFCI breakers
®
Page 11
115 VAC
10 AWG
(5.3mm
)
2
®
(NEC
) and
®
)
®