3.2
Electrical connection
Important :
personnel. Check that the cable supplying the technical room has a sufficiently large cross-section
to support the additional consumption required by the machine.
The heat pump must be supplied from an independent D-curve circuit breaker which can be either on
the main electrical panel equipped with a differential or on an independent panel connected to the main panel,
which will have a differential. If this is not the case, add a differential to the independent panel of your heat pump.
Reference
E35 INV
E55 INV
E75 INV
E95 INV
Electrical connection on the terminal block of the heat pump
Monophase
Unscrew the handle to access the electrical connection
The connection of your heat pump must be carried out by authorised and qualified
Power circuit
Power supply
breaker curve D
Monophase 230 V
10 Amps
Monophase 230 V
16 Amps
Monophase 230 V
16 Amps
Monophase 230 V
25 Amps
Cable section according to the distance
between circuit breaker and PAC
- 10 m
10 -15 m
3G1.5 mm2
3G1.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
3G2.5 mm2
Three-phase
L :
Line
N :
Neutral
:
Earth
+ 15 m
3G2.5 mm2
3G6 mm2
3G6 mm2
3G6 mm2
35