2.6 High water temperature alarm

A maximum allowed water temperature value can be specifi ed for safety reasons. If the heat exchanger
outlet temperature exceeds the set threshold, heat recovery will be deactivated. The diff erential represents
a hysteresis for resetting the alarm.
2.7 Analogue input fi lter

2.8 Second heat recovery module

Screens Eeab15 to Eeab21 can be used to confi gure the second heat recovery module. The settings are
similar to those for the fi rst module.
Screen Eeab13 can be used to specify whether to apply a
fi lter (average of the samples) to the probe used to calculate
the heat recovery demand THRnO.