Features
Digital LED Display and
5
Load Meter (Ammeter)
3-Digit Display: Shows
A
measured or calculated
amperage, kilowatt or voltage
values.
Enter Button: Scroll through
B
DISPLAY and CONFIGURATION
options using this button. While
in DISPLAY mode, a short press
switches the display between
AMPS, KW and VOLTS. While in
CONFIGURATION mode, a long
press changes configuration
items (TEMPERATURE, AUTO
SCROLL, LED BRIGHTNESS).
Pressing the Enter button and
Mode button simultaneously
displays the unit's IP address
(select models).
Mode Button: A short press of this button cycles through each of the modes
C
(PRIMARY, SECONDARY, BANK, TEMP*, HUMIDITY*) of the present category
(DISPLAY or CONFIGURATION) for both primary and secondary inputs. A long
press switches between DISPLAY and CONFIGURATION. Pressing the Mode
button and Enter button simultaneously displays the unit's IP address (models
with WEBCARDLX installed).
*TEMP/HUMIDITY only available if optional ENVIROSENSE module is attached.
Active Input LEDs: Indicate whether the primary or secondary active input is
D
powering the output.
2-Digit Display: Indicates whether the value shown on the 3-digit display
E
represents primary, secondary, bank, temperature or humidity.
Display Modes:
P: The 3-digit display is showing information related to the primary AC input.
(Unit LEDs dictate what data is shown.)
S: The 3-digit display is showing information related to the secondary AC input.
(Unit LEDs dictate what data is shown.)
b 'n': The 3-digit display is showing information related to the output bank
number ('n').
t 'n': The 3-digit display is showing temperature for sensor ('n'). (Units for F or C
are configured in CONFIGURATION mode.)
h 'n': The 3-digit display is showing humidity for sensor ('n').
A
ACTIVE INPUT
D
AMP
PRIMARY SECONDARY
b = BANK
t = TEMP
h = HUMIDITY
E
13
F
B
KW
VOLT
C
P = PRIMARY
S = SECONDARY