5.4 Confi guration condensate drain
There are three modes of operation:
a) CAPACITIVE = Automatic drainign using a capacitive sensor;
b) TIMED = programmable draining times;
c) CONTINUOUS (external) = if there is an external drain.
esc
set
Press
and
together at the same time to enter general menu
"PAr" .
set
Press
to enter.
to fi nd menu " Cd "
Use the arrows
or
set
Press
to enter.
to fi nd parameter " d3 "
Use the arrows
or
set
Press
to choose the type of the drain:
0 = external;
1 = timed;
2 = capacitive.
set
Press
for fi ve seconds to select the drain.
esc
set
PAr
set
esc
CF9
........
d2
d3
set
esc
1
0
For the option (1) timed drain,it is possible to set the ON/OFF time of
the drain.
On menu " Cd "
Use the arrows
or
to fi nd the parameter "d1" to set the
opening time.
set
Press
to confi rm.
to fi nd the parameter " d2 " to set the
Use the arrows
or
closing time.
PSE 325-1000 60Hz
set
Press
to confi rm.
esc
Press
to exit.
5.5 Visualization of temperature probes
On display appear the dew point temperature as defoult.
To view other temperatures, proceed as follows:
Use the arrows
b0 = dew point temperature sensor;
b2 = evaporation temperature sensor;
b5 = Suction compressor temperature sensor;
b8 = condensation temperature sensor;
Pi = High pressure sensor
Once chosen wait a few seconds and the probe value will appear.
esc
Press
to exit.
b0
If you switch OFF the dryer with
you chose remains memorized.
If you switch OFF the dryer with the MAIN SWITCH "
Cd
switch ON returns to reading the B0 sensor.
5.6 Modbus ON/OFF
esc
set
set
Press
and
esc
"PAr" .
set
to enter on menu " CF9"
d1
Press
Use the arrows
"CF32"
set
Press
to enter.
2
PARAMETER
Modbus on / off enabling
Unit address
Baud rate
Protocol modbus
Modbus enabling
Enables the modbus function
Unit address
Give an address to your unit.
or
chosse the sensor.
b2
...
0.0
....
set
, when you switch ON the sensor
&
", when you
together at the same time to enter general menu
to fi nd parameter " A5 ", "CF30", "CF31",
or
CODE
TYPE
DEFAULT
A5
OFF
D
CF30
1
D
CF31
5
D
CF32
1
D
Baud rate
1
3
5
2400
9600
38400
2
4
6
4800
19200
57600
Protocol modbus
1 = EVEN; 2 = NONE; 3 = ODD
5.7 Remote ON/OFF
esc
set
Press
and
together at the same time to enter general menu
"PAr" .
set
to enter on menu " CF9"
Press
to fi nd parameter " A7 ".
Use the arrows
or
set
Press
to enter.
Use the arrows
or
to choose:
ON : remote ON;
OFF: remote OFF.
set
Press
to confi rm.
esc
Press
to exit.
esc
set
PAr
set
esc
CF9
set
esc
A1
esc
OFF
Y
To manage REMOTE OFF mode, remove the bridge between
terminals: 87 -GND and connect the remote start/stop switch (to be
provided for by the customer).
4/14
7
115200
A7
set
0n