7.5. GUIDE TO CONFIGURE THE INVERTER
USING THE DISPLAY.
The parameters that must be configured for start-up are as
follows:
BLUETOOTH/WIFI COMMUNICATION.
Communications are set to bluetooth by default, so you
ˆ
must change to WiFi if you want to connect the equip-
ment to the EQX-sun app. To do so, access the "General
Config." menu and then the "WiFi Conn." parameter.
WORK MODE.
To select the required work mode, access the "General
ˆ
Config." menu and then the "Adj. Work. Mode" param-
eter.
BATTERY TYPE.
If there are batteries, enter the type used. To do so,
ˆ
access the "General Config." menu and then the "Batt.
Ident." parameter. There are two types of compatible
battery manufacturers:
EQX_BATT: Salicru.
Pylon_HV: PylonTech.
CT TRANSFORMERS.
The CT ratio is configured automatically when the meter
ˆ
is detected. To configure it manually, access the "General
Config." menu and the "CT Ratio" parameter.
DEPTH OF DISCHARGE (DOD).
The DOD limits battery discharge to a minimum SOC (State
ˆ
of Charge) to protect the battery. For example, a DOD value
of 90% indicates that it will prevent further discharge
when the battery reaches 10% capacity. To configure it,
you must access the "Advanced Config." menu. Enter the
password "1111" and then configure the "Pr. SOC On-Gr."
and "Pr. SOC Off-Gr." parameters and enable the "On-Grid
DOD" and "Off-Grid DOD" parameters.
92
Options.
ZERO INJECTION.
Access the "General Config." menu to configure the
ˆ
following parameters:
In order not to dump the surpluses into the grid,
enable Zero Injection via the "P. Limit" parameter.
Set the "Export" parameter to 0%.
PEAKLOAD SHIFTING.
To enable the PeakLoad Shifting function, you must
ˆ
access the "Advanced Config." menu with the password
"1111", and enable the "NON-PEAK mode" parameter
and set the Pmax power limit with the "Grid Pmax. kVA"
parameter.
ECONOMY MODE PROFILE.
In order to use Economy mode, you must set a charge and
ˆ
discharge profile. To do so, access the "Advanced Config."
menu and set the following parameters for charging:
"Charging Start T.": Start time for charging
"Charging End T.": End time for charging
"Charging P. Lim.": Charging power limit
Access the "Advanced Config." menu and configure the
ˆ
following parameters for discharging:
"Discharging Start T.: Start time for discharging
"Discharging End T.": End time for discharging
"Discharging P. Lim.": Discharging power limit