6
To set the data of other item codes (DN),
press [
Set/Fix]
To not do other settings, press [
The changes are fixed, and the "Field setting
menu" screen returns.
" " appears while data is changing.
When doing group connections:
Press [
Return] to open the unit selection
screen. In the unit selection screen, press
[
Return] to briefly display " ", and then
return to the "Field setting menu" screen.
35-EN
Installing indoor unit on high
■
ceiling
Return]
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
1
2
3
4
5
6
(
→
→
→
→
→
).
3
• For the CODE No. in Procedure
, specify [5d].
• Select the SET DATA for Procedure
"Height list of ceiling possible to be installed" table in
this manual.
◆ Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. Board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. Board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
SET DATA
SW501-1
0000
OFF
(Factory default)
0001
ON
0003
OFF
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
Change of lighting time of
filter sign
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
1
2
3
4
(
For the CODE No. in Procedure
4
from the
For the SET DATA in Procedure
SET DATA of filter sign lighting time from the
following table.
SET DATA
0000
0001
0002
0003
0004
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow the basic operation procedure
1
2
3
4
(
For the CODE No. in Procedure
For the SET DATA in Procedure
SET DATA of shift value of detection temperature
to be set up from the table below.
SET DATA
0000
0001
SW501-2
0002
0003
OFF
0004
OFF
0005
ON
0006
– 18 –
Changing the wind direction
■
Up / down direction: Horizontal louvres
5
6
).
3
, specify [01].
4
, select the
Filter sign lighting time
None
150 H
2500 H (Factory default)
5000 H
10000 H
* Display while swinging
1
Press [
"Wind direction" screen (horizontal louvres)
2
Press [
direction
5
6
(1)
(2)
).
3
, specify [06].
4
, select the
Operation mode
Heat, Fan, Auto (Heat)
Cool, Dry, Auto (Cool)
Detection temp shift value
No shift
1.8°F (+1°C)
3.6°F (+2°C) (Factory default)
5.4°F (+3°C)
7.2°F (+4°C)
9.0°F (+5°C)
10.8°F (+6°C)
] and [
] to switch to the
] and [
] to select wind
(3)
(4)
(5)
Swing
Settable angles
(1), (2), (3), (4), (5), Swing
(1), (2), (3), Swing
EN
FR
ES
36-EN