Power supply wire
Recommended wire diameter and wire length for power supply wire.
Power supply wiring
Electric characteristics
Model
MMK-UP0301HP-UL
MMK-UP0361HP-UL
Control wire
Control wiring between indoor units, and outdoor unit
(2-core shielded wire)
Communication line
TU2C-Link models (U series) can be combined with TCC-Link models (other than U series).
For details of communication type, refer to the following table.
Communication type and model names
Communication
type
Outdoor unit
Indoor unit
Wired remote
controller
Wireless remote
controller kit &
receiver unit
U series outdoor unit : SMMS-u (MMY-MUP
Other than U series outdoor unit : SMMS-i, SMMS-e etc. (MMY-MHP
23-EN
Power Supply
208/230V-1-60Hz
TU2C-Link
(U series and future models)
MMY-MUP
This letter indicates U series model.
MM * -UP
This letter indicates U series model.
RBC-A U
This letter indicates U series model.
RBC-AXU
This letter indicates U series model.
Wire size: 2 × AWG12
Ground
1 × AWG12 or thicker
Voltage Range (V)
Min
Max
187
253
(Up to 3280'10" (1000 m)) AWG16
Wire size
(Up to 6561'8" (2000 m)) AWG14
Other than U series
MMY-MHP
MCY-MHP
MMY-MAP
Other than U series
MM -AP
Other than U series
Other than U series
)
– 23 –
Installation Manual
Up to 164'1" (50 m)
MCA
MOCP
(A)
(A)
0.83
15
0.83
15
TCC-Link
(Other than U series)
)