Refer to Tables 5-2&5-3 for the specifications of the power cord and communication wire. A wiring capacity that is too small will cause the
electrical wiring to become too hot, and lead to accidents when the unit burns and becomes damaged.
Select the wire diameters( minimum value) individually for each unit based on the table 5-3.
Maximum allowable voltage range variation between phases is 2%.
Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection where MFA is used to select
the current circuit breakers and residual current operation breakers:
Rated current of appliance A
≤3
>3
and
≤6
>6
and
≤10
>10
and
≤16
>16
and
≤25
>25
and
≤32
>32
and
≤50
>50
and
≤63
Table 5-2
Model
Phase
Power
supply
Volt and frequency
Communication wire between
indoor unit and wired controller *
CIRCUIT BREAKER/FUSE(A)
Please refer to the corresponding wired controller manual for the wired
controller wiring.
MISTRALSU15---MISTRALSU80
1-phase
220-240V~50/60Hz
Shielded
3×AWG16-AWG18
15/15
Table 5-3
Nominal cross-sectional area (mm )
Flexible cords
0.5 and 0.75
0.75
and
1
1
and
1.5
1.5
and
2.5
2.5
and
4
4
and
6
6
and
10
10
and
16
15
2
Cable for fixed wiring
1
and
2.5
1
and
2.5
1
and
2.5
1.5
and
4
2.5
and
6
4
and
10
6
and
16
10
and
25
V.1