Settings – Menu (5 of 6) | Temp, Motor, Settings and Ramps
Main Menu
Sub Menu
*** To save any changes, press
= scroll menu items
*** To the previous step without saving, press
M ain M enu
PrSs
(Pressure)
APPS
(Applications)
InPt
(Inputs)
OutP
(Outputs)
tMp
(Temperature)
Mot
(Motor)
Setc
(Settings)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
btN
(Buttons)
https://www.innes.com.mx/
on INTRM24VAV***
on INTRM24VAV***
= select / set value
Int er n T em p Sensor O f f set
E xt er n Tem p S ensor O f f set
Actual temp °C/°F
Actual temp °C/°F
AV.10
AV.11
(± 5°C / ± 10°F)
(± 5°C / ± 10°F)
Appears only if AI1 or AI2 = EtS
= select / set value
M ot or Signal Ram p
MSV.35
OFF~
Cr1
(cooling ramp 1)
M ot or DIR -RE V
BV.40
Cr2
(cooling ramp 2)
DIR
(direct)
Hr1
(heating ramp 1)
REV
(reverse)
Hr2
(heating ramp 2)
StF
l (stpnt airflow 0-10Vdc)
Cor
(changeover ramp)
CH1
(cool/heat)
ANLg
(analog 0-10Vdc)
= select / set value
BV.3
Tem p C ont r ol M ode
MSV.17
E nabl e onof f C ont r ol M ode
Auto
(automatic all modes)
No
(Disabled)
HEAt
Yes
(heat/off)
(Enabled)
COOl
(cool/off)*
ON
(manual heat/cool)
CLHt
(auto/off)
C l Ht S wit ch T im e in M inut es
0 min
AV.170
(0-120 min)
= scroll menu items
Ram p Set t ing
COr
(changeover)
C H O ver Pr op Band
Cr1
(cooling ramp 1)
2.0°C / 4.0°F
Cr2
(cooling ramp 2)
Hr1
C R 1 Pr op B and
(heating ramp 1)
Hr2
2.0°C / 4.0°F
(heating ramp 2)
CO2
(carbon dioxide)
C R 2 P r op Band
2.0°C / 4.0°F
Hr 1 Pr op Band
2.0°C / 4.0°F
Hr 2 P r op Band
2.0°C / 4.0°F
C O 2 C O NT RO L M O DE
OPEn
Ctrl
Configuration
User M inim um Set pnt
User M axim um Set pnt
15.0°C / 59°F
30.0°C / 86°F
AV.16
(10°C-AV.17 / 50°F-AV.17)
(AV.16-40°C / AV.16-104°F)
User S et pnt
Tem p C ont r ol S ensor
22.0°C / 72°F
AV.15
ItS
(internal sensor)
EtS
(Av.16 – AV.17)
(external sensor)
NEt
(network)
AVE
(average temp)
mA
(maximum temp)
EtS appears only if AI1 or AI2
is set to EtS
M ot or Faul pos
BV.41
CLOS
(close)
Go to "SEtc"
OPEn
(open)
Displ ay Inf o
MSV.95
Fr eeze Pr ot ect
t°c
No
(Disabled)
(temp & demand)
StP
Yes
(setpoint & demand)
(Enabled)
t°c
(temp only)
StP
(setpoint)
OFF
(no display: blank)
Air f l ow Int gr al t im e in M in
Heat ing Int gr al t im e in Sec
0 min
0 sec
AV.106
(0-60 min)*
(0-250 sec)
AV.56
C H O ver Dead B and
AV.57
0.3°C / 0.6°F
(0.5-5°C / 1-9°F)
(0-5°C / 0-9°F)
C R 1 D ead Band
AV.41
AV.42
0.3°C / 0.6°F
(0.5-5°C / 1-9°F)
(0-5°C / 0-9°F)
AV.46
C R 2 Dead B and
AV.47
0.3°C / 0.6°F
(0.5-5°C / 1-9°F)
(0-5°C / 0-9°F)
Hr 1 Dead B and
AV.21
AV.22
0.3°C / 0.6°F
(0.5-5°C / 1-9°F)
(0-5°C / 0-9°F)
AV.24
Hr 2 D ead Band
AV.25
0.3°C / 0.6°F
(0.5-5°C / 1-9°F)
(0-5°C / 0-9°F)
BV.101
Go to "NEt"
(open)
(control)
AV.190
C O 2 P r op B and
100 ppm
(50-250 ppm)
INCTR14VAV Standard
Controlador de VAV
Manual de especificación e Instalación
User S et pnt Locked
BV.2
No
AV.17
(unlocked)
Yes
(locked)
MSV.4
Go to "mot"
Net w or k t im eout M inut es
Go to "mot"
5 min
(0-60 min)
AV.145
Tem p Aver age
MSV.45
Go to "mot"
TA1
(TSTAT+AI1)
TA2
(TSTAT+AI2)
TA-
(TSTAT+AI1+AI2)
A-
(AI1+AI2)
BV.6
C ool ing ant i cycl e m inut es
2 min
(0-15 min)
AV.51
Go to
C ool ing Int gr al t im e in S ec
"rMp"
0 sec
AV.30
AV.50
(0-250 sec)
Go to "Cr1"
Go to "Cr2"
Go to "Hr1"
Go to "Hr2"
Go to "CO2"
Go to "NEt"
C O 2 DE AD Band
AV.191
20 ppm
(10-50 ppm)
Page | 11