Anexo A: Control Apps
Refer to Pressure & Applications – Menu (1 of 6) on page 7 for more information. The available Control Apps vary according to the
model.
CL
Description
(cool only)
Min. Setpoint
20°C (68°F)
Max. Setpoint
28°C (82°F)
Changeover Setpnt
24°C (75°F)
TO1 Ramp
HR1
TO1 Signal Type
On/Off
TO1 Close Pos.
40%
TO1 Open Pos.
0%
TO2 Ramp
HR1
TO2 Signal Type
Pulse
TO2 Close Pos.
40%
TO2 Open Pos.
0%
TO3 Ramp
HR2
TO3 Signal Type
On/Off
TO3 Close Pos.
40%
TO3 Open Pos.
0%
TO4 Ramp
HR2
TO4 Signal Type
Pulse
TO4 Close Pos.
40%
TO4 Open Pos.
0%
Motor Ramp
CR1
AO1 ramp
HR1
AO2 Ramp
HR2
AI1 Input
OFF
AI2 Input
OFF
DI1 Input
nSb.o
Heat Prop Band 2
2°C (4°F)
Heat Deadband 2
1.3°C (2.6°F)
Cool Deadband 2
1.3°C (2.6°F)
Legend
Grey Text
= Standard default value
Bold Text = Special default value for selected application
HR
= Heating ramp
CR
= Cooling ramp
COr
= Changeover ramp
SENS
= Changeover temperature sensor
Fan ON
= Fan powered box in continuous mode
Fan Auto = Fan powered box in automatic mode (follows demand)
nSb.o
= Night Setback (normally open)
Occ.o
= Occupancy mode (normally open)
TO
= TRIAC output
AO
= Analog output
AI
= Analog input
DI
= Digital input
https://www.innes.com.mx/
CLHt
CHrH
(cool/heat)
(cool/heat/reheat)
20°C (68°F)
20°C (68°F)
28°C (82°F)
28°C (82°F)
20°C (68°F)
20°C (68°F)
CR1
HR1
On/Off
On/Off
40%
40%
0%
0%
HR1
HR1
On/Off
Pulse
40%
40%
0%
0%
CR2
HR2
On/Off
On/Off
40%
40%
0%
0%
HR2
HR2
On/Off
Pulse
40%
40%
0%
0%
COr
COr
CR1
HR1
HR1
HR2
SENS
SENS
OFF
OFF
nSb.o
nSb.o
2°C (4°F)
2°C (4°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
INCTR14VAV Standard
Controlador de VAV
Manual de especificación e instalación
CO
ITOS
2
(CO
)
(ITOS)
2
20°C (68°F)
15°C (59°F)
28°C (82°F)
30°C (86°F)
20°C (68°F)
24°C (75°F)
CR1
OFF
On/Off
On/Off
40%
40%
0%
0%
CO
OFF
2
On/Off
On/Off
40%
40%
0%
0%
HR1
OFF
On/Off
On/Off
40%
40%
0%
0%
HR1
OFF
On/Off
On/Off
40%
40%
0%
0%
COr
CR1
CR1
HR1
HR1
OFF
SENS
OFF
CO
OFF
2
Occ.o
Occ.o
2°C (4°F)
2°C (4°F)
1.3°C (2.6°F)
0.3°C (0.6°F)
1.3°C (2.6°F)
0.3°C (0.6°F)
FPbo
FPbA
(fan powered ON)
(fan powered Auto)
15°C (59°F)
15°C (59°F)
30°C (86°F)
30°C (86°F)
24°C (75°F)
24°C (75°F)
HR1
HR1
On/Off
On/Off
35%
35%
0%
0%
HR1
HR1
On/Off
On/Off
70%
70%
35%
35%
Fan ON
Fan Auto
On/Off
On/Off
40%
40%
0%
0%
HR1
HR1
On/Off
On/Off
40%
40%
0%
0%
CR1
COr
HR1
HR1
HR2
Fan Auto
OFF
SENS
OFF
OFF
nSb.o
nSb.o
1°C (2°F)
1°C (2°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
0.3°C (0.6°F)
0.3°C (0.6°F)
Page | 17