Descargar Imprimir esta página

Innes INCTR14VAV Manual De Instalación página 9

Publicidad

Idiomas disponibles

Idiomas disponibles

TRIAC Outputs – Menu (3 of 6) | TO1 to TO4
Main Menu
Sub Menu
= scroll menu items
M ain M enu
PrSs
(Pressure)
APPS
(Applications)
= scroll menu items
O ut put C onf ig
TO1
TO2
InPt
(Inputs)
TO3
TO4
AO1
OutP
(Outputs)
AO2
tMp
(Temperature)
Mot
(Motor)
Setc
(Settings)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
btN
(Buttons)
https://www.innes.com.mx/
*** To save any changes, press
on INTRM24VAV***
*** To the previous step without saving, press
= select / set value
TO1
TO 1 Ram p
MSV.25
OFF
Go to "TO2"
Cr1
TO 1 Signal Type
(cooling ramp 1)
Cr2
OnOf
(on/off)
(cooling ramp 2)
Hr1
FLt
(heating ramp 1)
(floating)
PuLs
Hr2
(pulsed) *
(heating ramp 2)
* = Only if Hr1 or Hr2 is selected
CO2
(carbon dioxide)
= select / set value
TO2
TO 2 Ram p
MSV.27
OFF
Go to "TO3"
Cr1
(cooling ramp 1)
Cr2
(cooling ramp 2)
TO 2 S ignal T ype
Hr1
(heating ramp 1)
OnOf
(on/off)
Hr2
(heating ramp 2)
PuLs
(pulsed)
CO2
(carbon dioxide)
= select / set value
TO3
TO 3 Ram p
MSV.29
Go to "TO4"
OFF
Cr1
(cooling ramp 1)
TO 3 Signal Type
Cr2
(cooling ramp 2)
OnOf
(on/off)
Hr1
(heating ramp 1)
FLt
(floating)
Hr2
(heating ramp 2)
PuLs
(pulsed) *
CO2
(carbon dioxide)
* = Only if Hr1 or Hr2 is selected
= select / set value
TO4
TO 4 Ram p
MSV.31
OFF
Go to "AO1"
Cr1
(cooling ramp 1)
Cr2
TO 4 S ignal T ype
(cooling ramp 2)
Hr1
OnOf
(heating ramp 1)
(on/off)
Hr2
PuLs
(heating ramp 2)
(pulsed)
CO2
(carbon dioxide)
INCTR14VAV Standard
Configuration
on INTRM24VAV***
If CO
was selected
2
TO 1 C l ose Per cent
40%
AV.77
(15-80%)
MSV.26
TO 1 -TO 2 F l oat ing Tim e in Sec
100 sec
(15 to 250/420§ secs)
AV.75
TO 2 C l ose P er cent
40%
AV.79
(15-80%)
MSV.28
If CO
was selected
2
TO 3 C l ose Per cent
MSV.30
40%
AV.81
(15-80%)
TO 3-TO 4 F l oat ing Tim e in Sec
100 sec
AV.76
(15 to 250/420§ secs)
TO 4 C l ose P er cent
TO 4 O pen Per cent
MSV.32
40%
AV.83
0%
(15-80%)
Controlador de VAV
Manual de especificación e Instalación
TO 1 DIR-RE V
DIR
(direct)
TO 1 O pen P er cent
REV
(reverse)
0%
AV.78
[0-(TO1 cls pos-4)]
TO 1 -TO 2 DIR -RE V
DIR
(direct)
REV
(reverse)
TO 2 O pen Per cent
TO 2 DIR -RE V
0%
AV.80
DIR
[0-(TO2 cls pos-4)]
(direct)
REV
(reverse)
TO 3 DIR -RE V
DIR
(direct)
TO 3 O pen P er cent
REV
0%
(reverse)
AV.82
[0-(TO3 cls pos-4)]
TO 3-TO 4 DIR -RE V
DIR
(direct)
REV
(reverse)
TO 4 DIR -RE V
AV.84
DIR
[0-(TO4 cls pos-4)]
(direct)
REV
(reverse)
Go to
BV.32
"TO2"
Go to
BV.30
"TO3"
Go to
BV.33
"TO3"
Go to
BV.34
"TO4"
Go to
BV.31
"AO1"
Go to
BV.35
"AO1"
Page | 9