0.8~1.0 m
a
b
b
<200mm
6.2 Drainage test
Check whether the drainpipe is unhindered
New built house should have this test done before paving
the ceiling.
1 Remove the test cover, and stow water of about 2000ml
to the water receiver through the stow tube. (Refer to Chart
19)
2 Turn on the power, and operate the air conditioner
under the "COOLING" mode. Listen to the sound of the
drain pump. Check whether the water is discharged well (a
lag of 1min is allowed before discharging, according to the
length of the drain pipe), and check whether water
leaksfrom the joints.
CAUTIONS: If there is any malfunction, please resolve it
immediately.
3 Stop the air conditioner for there minutes, check if
everything is ok. If the drain hose is located unreasonable,
water overflow will cause the Alarm indicator lamp flashing
(For both cooling and heating type or cooling only type),
even the water leak out from the water receiver.
4 Check the drain pump whether drain water immediately
when alarm sound for the high water lever. If the water
lever can't come down below to the limited water lever, the
air conditioner will stop. Restart it until turn off the power
and drain off all the water.
5 Turn off the power, drain the water away.
The drain plug is used to empty the water-receiver for maintenance
of the air conditioner. Please stuff it imposition at all times during
operation to avoid leakage.
Gradient:
higher than 1/100
>1.0 m
Fig.6-1
0.8-1.0m
Lean over 1/100
Pump-pipe clasp
(the fittings)
Fig.6-2
7. WIRING
CAUTION
The air conditioner should use separate power supply with
rated voltage.
The external power supply to the air conditioner should
have ground wiring, which is linked to the ground wiring of
the indoor and outdoor unit.
The wiring work should be done by qualified persons
according to circuit drawing.
an all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
rule.
The appliance shall be installed in accordance with
national wiring regulations.
Be sure to locate the power wiring and the signal wring well
to avoid cross-disturbance.
Do not turn on the power until you have checked carefully
after wiring.
Remark per EMC Directive 2004/108/EC
For to prevent flicker impressions during the start of the
compressor (technical process), following installation
conditions do apply.
1
The power connection for the air conditioner has to be
done at the main power distribution. The distribution has
t o b e o f al o w i m p e d a n c e , n o r m a l l y t h e r e q u i r e d
impedance reaches at a 32 A fusing point.
2
No other equipment has to be connected with this power
line.
3
For detailed installation acceptance please refer to your
power supplier, if restrictions do apply for products like
washing machines, air conditioners or electrical ovens.
For power details of the air conditioner refer to the rating
4
plate of the product.
5
For any question contact your local dealer.
7.1 Connect the cable
Dissemble the bolts from the cover.(If there isn't a cover on
the outdoor unit, disassemble the bolts from the maintenance
board, and pull it in the direction of the arrow to remove the
protection board.)
Connect the connective cables to the terminals as identified
with their respective mached numbers on the terminal block
of indoor and outdoor units.
Re-install the cover or the protection board.
V.1
NOTE
installation manual
7