3AUA0000088632
Unfasten the insertion ramp and attach the LCL filter module to bottom plate.
Attach the drive module pedestal guide plate to the cabinet bottom plate.
Attach the telescopic insertion ramp to the pedestal guide plate.
Remove the sheeting from the clear plastic shrouds of the drive module from both
sides.
Install the top metallic shroud to the drive module.
Install the back shrouds to the drive module.
To prevent the drive module from falling, attach its lifting lugs with chains to the cabinet
frame.
Push the drive module carefully into the cabinet along the telescopic insertion ramp.
Work preferably with help from another person. Keep a constant pressure with one
foot on the base of the module to prevent the module from falling on its back.
Unfasten the insertion ramp and attach the drive module to the bottom plate.
Attach the LCL filter module and drive module to the punched section.
Attach LCL filter module to the drive module from top side. Reinstall the cover.
Connect the LCL filter busbars to the drive module busbars with the connecting
busbars.
Connect the LCL filter fan power supply cable to connector FAN3:LCL.
Connect the power cables and install the shrouds as described in section
the power cables and installing the
Install the external control unit and connect the control cables.
Install the air baffles.
Connecting the power cables and installing the shrouds
Step
1
Install the grounding terminal to the drive module base.
2
Run the motor cables to the cabinet. Ground the cable shields 360 degrees at the cabinet entry.
3
Connect the twisted shields of the motor cables to the grounding terminal.
EN – Quick installation guide 5
shrouds.
Task (motor cables)