122 Technical data and references
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Losses, cooling data and noise
Frame
ACH580-04...
size
505A-4
R10
585A-4
R10
650A-4
R10
725A-4
R11
820A-4
R11
880A-4
R11
1) Typical drive losses when it operates at 90% of the motor nominal frequency and 100% of the motor nominal
current.
Typical power cable sizes
The table below gives copper and aluminium cable types with concentric copper shield
for the drives with nominal current. See also section
power cables (page
ACH580-04-...
U
= 400 V
n
505A-4
585A-4
650A-4
725A-4
820A-4
880A-4
U
= 480 V
n
505A-4
585A-4
650A-4
725A-4
820A-4
880A-4
1) The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
Air flow
3
m
/h
1200
1200
1200
1200
1200
1420
123).
Cu cable
2
mm
3 × (3×95)
3 × (3×120)
3 × (3×150)
3 × (3×185)
3 × (3×240)
3 × (3×240)
3 × (3×95)
3 × (3×95)
3 × (3×120)
3 × (3×150)
3 × (3×185)
3 × (3×240)
Typical power
cfm
707
707
707
707
707
848
Terminal and entry data for the
1)
IEC
Al cable
mm
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
4 × (3×240)
3 × (3×150)
3 × (3×150)
3 × (3×185)
3 × (3×240)
4 × (3×185)
4 × (3×240)
Noise
1)
loss
W
dB(A)
6492
72
6840
72
8046
72
8108
72
9652
72
10887
71
2

Publicidad

loading