Owner's Manual
Philips screwdriver
10 mm wrench
6 mm hex bit and T45 bit
¼ in. nut driver
Cleaning cloths
HEPA vacuum cleaner with soft brush nozzle and crevice nozzle.
Recommended
Cordless drill, small knife, small-jaw pliers, coil cleaning solution, rotomolded
housing cleaning solution.
BEFORE EACH USE
Inspect the electrical cord for damage. Look for fraying, cuts, etc. Do not use the
unit if you find any damage. Contact your local authorized distributor for service.
Inspect filter. The PHD 200 filter should be replaced when the accumu-lation of dust
is visible.
MONTHLY
Clean pump check valve and basin. In normal use, dust can accumulate and can
restrict air-flow, reducing performance and causing the unit to over-heat. Clean when
dust accumulation is visible. Remove grills and cover as shown in Fig. B. Use a vacuum
cleaner with a brush tool and a soft cloth to remove any debris. Take care not to
damage any interior components.
To maintain appearance, wipe interior and exterior surfaces with a damp cloth. For
deep cleaning and a lasting, protective shine, use an automotive interior cleaner.
AS NEEDED
Clean pump check valve and basin. Remove grills and cover as shown in Fig. B.
Remove screws from pump base and lift out pump. Wipe out pump basin with a
damp cloth. Inspect the pump base for build-up of debris and clean if needed.
Unthread barbed fitting with check valve and rinse fitting and check valve with clean
water. Reinstall check valve into barbed fitting and install the barbed fitting into pump.
Do not overtighten. Reinstall pump on base. Reinstall cover and grills.
Clean coils. With the cover removed, inspect both coils. If excessive dust and debris is
present, vacuum thoroughly and/or clean with coil cleaner.
PHD 200 Owner's Manual
19
© 2023 Legend Brands, Inc.