4.4.1.2 Alarm relay management
0
Relay normally deactivated, excited by an alarm.
Relay normally excited (also with control OFF), deactivated
1
by an alarm.
Relay normally excited (only with control ON), deactivated
2
by an alarm or with control OFF.
4.4.2
Temperature control
PARAMETER
CODE
Temperature control set point
SEt
Temperature control set point
SEt
" CPt= On"
dIF
Temperature control differential
LI5
Set point lower limit
4.4.3
B1 sensor parameters
PARAMETER
CODE
cHAI
High temperature confi guration
HAI
High temperature alarm
LAI
Low temperature alarm
CAI
Sensor calibration
Low temperature alarm reset
dbI
differential
4.4.4
B2 sensor parameters
PARAMETER
CODE
cHA2
High temperature confi guration
HA2
High temperature alarm
LA2
Low temperature alarm
CA2
Sensor calibration
Ab2
B2 sensor presence
English
4.4.5
B3 sensors parameters
PARAMETER
High temperature alarm
Low temperature alarm
Sensor calibration
TYPE
DEFAULT
4.4.6
Compressor parameters
7.0
D
PARAMETER
44.6
Compressor operation hour counter
20.0
D
Compressor hour counter threshold
68.0
4.4.7
Pump parameters
4.0
D
7.2
PARAMETER
Pump stop delay
5.0
U
Pump start delay
41.0
4.4.8
Antifreeze heater parameters
PARAMETER
TYPE
DEFAULT
0
U
Set point adjustment (B1)
60.0
D
140.0
Temperature control differential (B1)
-20.0
D
Antifreeze heater operating mode
-4.0
(see para. 4.4.8.1)
0.0
U
Antifreeze heater activation mode
1.0
(see para. 4.4.8.2)
U
1.8
Activation set point (B3)
4.4.8.1 FUA antifreeze heater operating mode
TYPE
DEFAULT
Temperature control by B1, activation by B3 (ambient
0
0
U
temperature sensor)
60.0
Temperature control by B3 (ambient temp. sensor) with
1
U
ARA set point.
140.0
4.4.8.2 AbrA antifreeze heater activation mode
3.0
U
37.4
0
Activation only when controller is 'On'
0.0
1
U
Activation also when controller is 'Off'
1.0
U
Activation also when controller is 'Off'. During heater opera-
2
tion the pump is activated.
CODE
TYPE
DEFAULT
60.0
HA3
U
140.0
-20.0
LA3
U
-4.0
CA3
0.0
U
CODE
TYPE
DEFAULT
HI
-
D
tHI
0
U
CODE
TYPE
DEFAULT
dP5
5
U
dPA
5
U
CODE
TYPE
DEFAULT
7.0
SEA
U
45.0
1.0
dIA
U
1.8
FUA
0
U
AbrA
2
U
5.0
ArA
U
41.0
PCW040-160
4.5 Parameter management
4.5.1
Temperature setting (see fi g.1)
1. 1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press buttons "P3" and "P5" together, to enter into "dIrE" (D)
parameters.
3. Press button "P4" to select "SEt" parameter, press the button
"P5" to confi rm.
4. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P5" to confi rm.
6. Press the button "P3" to return on "dIrE" parameter.
7. Press the button "P5" to exit.
4.5.2
Differential setting (see fi g.1)
1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press buttons "P3" e "P5" together, to enter into "dIrE" (D)
parameters.
3. Press button two times "P4" to select "diF" parameter, press the
button "P5" to confi rm.
4. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P5" to confi rm.
6. Press the button two times "P3" to return on "dIrE" parameter.
7. Press the button "P5" to exit.
4.5.3
Visualization sensors B1,B2...
"B1" is the "set" sensor of the macchine.
1. Start the chiller.
2. Press the button "P4" to visualize the temperature of the next sen-
sor.
3. Press the button "P5" to visualize the sensors "b01" .."b02"....
It is recommended to leave on the display the B1 "set" sensor.